Document No. 129-479 
Installation Instructions 
November 13, 2012 

Mounting Information 

Always mount the room unit vertically. 
 
Locate the room unit: 

 

according to design specifications and local 
regulations. 

 

where the air circulates around it freely (not 
in recessed areas or behind doors). 

 

allowing a minimum of 4 inches (10 cm) free 
space above and below for proper airflow, 
the front cover removal tool, and the 
computer communication cable. 

 

away from drafts caused by doors, windows, 
outside walls, air registers, pipes, return air 
plenums, etc. 

 

away from heat sources such as strong 
lights, fireplaces, direct sunlight, etc. 

 

on an inside wall (preferably), about 5 feet 
(1.5 m) above the finished floor. 

Drywall Mounting (No Rough-in), 
Typical 

Base Plate Mounting and Wiring 

1.  Mark the center (cable) hole and the mounting 

hole locations, using the room unit base plate as 
a template. See Figure 2.  

2.  Drill two 3/16-inch (4.8 mm) mounting holes and 

mount the two plastic wall anchors flush to 
below the wall surface for stable mounting of the 
device. 

3.  Cut a 1-inch (25 mm) center hole with a hole 

saw. 

4.  Pull about three inches (75 mm) of the cable 

through the hole in the base plate. 

5.  Mount the room unit base plate on the wall, 

noting the UP arrow: 

NOTE: 

If required, position the Back Plate 
behind the Room Unit Base, aligning 
the top and bottom mounting holes, 
prior to mounting to the wall: 

a.  Install the two mounting screws provided, 

but do not tighten. 

b.  Level the room unit base plate for 

appearance. 

c.  Tighten the two mounting screws to the 

room unit base plate. 

d.  Cut the cable, leaving about three inches 

(75 mm) on the room unit side of the 
drywall. Ensure that pin Number 1 connects 
to the same wire at each end of the cable.  

 

Figure 2.  Drywall Mounting (No Rough-in), Typical. 

7.  Terminate the wires to the termination blocks on 

the room unit's base plate. (See Figure 5.) 

8.  Feed the extra cable back through the hole. 

Sensor Set-up 

SEN0589R1

5V

10V

V

I

Jumper

R64 Resistor

(°F/°C Selector)

Voltage/Current
Selector Switch

 

Figure 3.  Circuit Board  

(Located inside Room Unit Cover. 

Page 2 of 6

 

Siemens Industry, Inc.

 

Содержание Series 2300

Страница 1: ...QAA2330 xWxx QAA23SS xWxN QAA23SS xWxx Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Expected Installation...

Страница 2: ...o plastic wall anchors flush to below the wall surface for stable mounting of the device 3 Cut a 1 inch 25 mm center hole with a hole saw 4 Pull about three inches 75 mm of the cable through the hole in the base plate 5 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior t...

Страница 3: ... locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of the room unit cable through the hole in the base plate 3 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior to mounting to the wa...

Страница 4: ...or Controller a 500 ohm resistor must be wired in series with the setpoint termination on the Predator Controller and the Override termination 8 on the Room Sensor See Figure 6 and Figure 7 for the complete wiring diagrams for the two different style controllers The installation is now complete 1 2 3 4 5 6 7 8 9 10 11 12 SEN0485R1 Figure 5 Typical Wiring Base All terminals may not be present Pin N...

Страница 5: ...0644R1 500 ohm Orange White Orange White Green White Blue Blue Green 5 SetPoint Bypass 6 Room Temp 2 LonNetwork 4 Common 3 Service Pin LCD Power 1 LonNetwork Color Pin Wire Twisted Pair Twisted Pair Twisted Pair P I 9 11 Figure 7 Pin No Function QAA2312 EWTN 2 Temperature 3 Temp_Common QAA2330 EWxC 2 Temperature 3 Temp_Common 7 LON1 8 LON2 QAA23SS EWxN 1 DC or ACH 2 DC or ACN GND 3 Temperature Out...

Страница 6: ...300 100 VA DC ACH DC ACN GND Signal Out Powered By Class 2 100VA Isolated AC L N E With Class 2 100 VA Output Isolated AC Supply See Controller Installation Instructions L N E Note See Caution NOTE Externally AC powered 2300 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same controller with other room units powered by internal sen...

Отзывы: