Appendix 

 

A.4 Sensor registers 

 

7KT PAC1200 multichannel current measuring system 

80

 

System Manual, 11/2016, 2514374103-02 

Sensor registers 

 

 

Start 

address 

(deci-

mal) 

End 

address 

(deci-

mal) 

Start 

address 

(hexa-

decimal) 

End 

address 

(hexa-

decimal) 

Size 

R/W Func-

tion 

codes 

Type 

Units  OBIS code 

Descrip-

tion 

Source 

type 

61440 

61443 

0xF000 

0xF003 

RO  0x10 

 — 

 — 

 — 

(re-

served) 

 — 

61444 

61447 

0xF004 

0xF007 

RO  0x10 

Unit 64  — 

0-x:96.1.1*255  Serial 

number 
+sensor 

index 

con-

figured 

61448 

61448 

0xF008 

0xF008 

RO  0x03 

Unit 16  — 

 — 

Phase 

(1, 2, 3) 

con-

figured 

61449 

61452 

0xF009 

0xF00C  4 

RO  0x03 

Unit 64  1 Wh  1-x:1.8.0*255 

Active 

power + 

cal-

culated 

61453 

61456 

0xF00D  0xF010 

RO  0x03 

 — 

 — 

 — 

(re-

served) 

 — 

61457 

61460 

0xF011 

0xF014 

RO  0x03 

Unit 64  1 VAh  1-x:9.8.0*255 

Apparent 

 

cal-

culated 

61461 

61464 

0xF015 

0xF018 

RO  0x03 

 — 

 — 

 — 

(re-

served) 

 — 

61465 

61466 

0xF019 

0xF01A  2 

RO  0x03 

Unit 32  0.001 

1-x:1.4.0*255 

Active 

power + 

cal-

culated 

61467 

61468 

0xF01B  0xF01C  2 

RO  0x03 

 — 

 — 

 — 

(re-

served) 

 — 

61469 

61470 

0xF01D  0xF01E  2 

RO  0x03 

Unit 32  0.001 

VA 

1-x:9.4.0*255 

Apparent 

 

cal-

culated 

61471 

61472 

0xF01F  0xF020 

RO  0x03 

 — 

 — 

 — 

(re-

served) 

 — 

61473 

61474 

0xF021 

0xF022 

RO  0x03 

Unit 32  0.001 

1-x:11.4.0*255  Current 

Sensor 

61475 

61476 

0xF023 

0xF024 

RO  0x03 

Unit 32  0.001 

1-x:12.4.0*255  Current 

potential 

Internal  

61477 

61478 

0xF025 

0xF026 

RO  0x03 

Unit 32  0.001  1-x:13.4.0*255  Power 

factor 

Internal  

61479 

61479 

0xF027 

0xF027 

RO  0x03 

 — 

 — 

 — 

(re-

served) 

 — 

Содержание SENTRON 7KT PAC1200

Страница 1: ...System Manual SENTRON Multi channel current measuring system 7KT PAC1200 Edition siemens com lowvoltage 11 2016 ...

Страница 2: ......

Страница 3: ...______________ ___________________ ___________________ PAC Measuring Devices 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 Introduction 1 Safety notes 2 Product description 3 Connection 4 Operator control software 5 Service and maintenance 6 Technical data 7 Appendix A ESD guidelines B ...

Страница 4: ...be operated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNIN...

Страница 5: ...erator control software 27 5 1 Browser based web application 27 5 1 1 System environment 27 5 1 2 Function overview 28 5 1 3 Home page 29 5 1 4 Statistics 30 5 1 5 Current values 31 5 1 6 Installment 32 5 1 7 Energy stopwatch 34 5 1 8 Settings 35 5 1 8 1 Start 35 5 1 8 2 Device 36 5 1 8 3 Sensors 36 5 1 8 4 Network Settings 39 5 1 8 5 Data export 40 5 1 8 6 Firmware update 43 5 1 8 7 Tariff settin...

Страница 6: ...l 55 7 Technical data 57 7 1 Dimension drawings 60 7 1 1 Dimensions of the Data Manager 60 7 1 2 Dimensions of the sensor bar 61 7 1 3 Dimensions of the sensors on the sensor bar 65 A Appendix 67 A 1 FAQs 67 A 2 Modbus register list 68 A 3 Internal registers 68 A 4 Sensor registers 79 B ESD guidelines 81 B 1 Electrostatic sensitive devices ESD 81 Glossary 83 Index 85 ...

Страница 7: ...ribed via the web server Target group The tasks described in this document must only be carried out by persons with the following electrical training qualifications Training in the installation und commissioning of electrical devices Training in electrical hazards and local safety regulations Knowledge of the relevant standards and guidelines Further documents You can find further details in the f...

Страница 8: ......

Страница 9: ...and the installation components that carry mains voltage or use suitable insulation Always lay the data and power lines separately or in separate pipelines Observe EN 50174 2 here NOTICE Overvoltage Material damage If network cables are laid in the outdoor area overvoltages can arise as a result of lightning strikes for example The network cable must be safeguarded with suitable overvoltage protec...

Страница 10: ...Readme_OSS Data Manager For safety reasons it is forbidden to modify the product including the software or to install components that are not expressly recommended or marketed for this product Any use of the product other than the intended use described is considered improper use Impermissible modification conversions repairs or opening of the product are forbidden The enclosed documentation is a ...

Страница 11: ...rs or opening of the product are forbidden The enclosed documentation is a component part of the product and must be read observed and kept available at all times CAUTION Overvoltage Material damage Only safety extra low voltages may be connected to the sensor bar Laws and directives The following standards apply for this system EN 61010 1 2010 Safety requirements for electrical equipment for meas...

Страница 12: ......

Страница 13: ...f the system Mobile terminal device Web browser powermanager Power distribution Device for which current is being monitored The 7KT PAC1200 multichannel current measuring system is part of the energy management portfolio The system comprises several components that are described in this chapter Data Manager Sensor bar Sensors ...

Страница 14: ...nager can supply up to eight sensor bars The full configuration would thus be 8 sensor bars with 12 sensors each Value provided by the system The system makes energy consumption and the resulting costs transparent for a given installation The system can be adapted to individual needs and application scenarios In addition single sensors can be named individually and compared with each other The sys...

Страница 15: ...d on the load side downstream of the energy counter of the power supply company It is suitable only for use in the indoor area and it is approved for use in the member states of the EU Use the sensor bar only in accordance with the information given in the enclosed documentation Any other use can result in material damage and personal injury 3 2 Functions How the individual components of the syste...

Страница 16: ... makes them available via LAN Input N Status LED Input L3 Output L1 Input L2 Output L2 Input L1 Output L3 Reset button Connector for RS 485 expansions Sensor LED LAN connection Network LED Must be connected The connections L1 L2 L3 can be found both on the upper and lower sections plus an additional connection for N On the front you will find the connection for the LAN cable The connection for the...

Страница 17: ...racy of the voltage measurement of the Data Manager is 0 5 of the full scale value The overall accuracy of the Data Manager is 2 of the full scale value There are 3 LEDs on the device These indicate the operating status The Status LED indicates operational readiness the Network LED indicates the connection with the network and the Sensor LED indicates sensor readiness The energy is measured simult...

Страница 18: ...ely for the current sensors The current sensors are located directly on the miniature circuit breakers and they register the latest current values The conductors to be measured are run through the ring shaped opening in the current sensors to the connections of the miniature circuit breaker Up to eight sensor bars can be connected to one Data Manager With the sensor bar with twelve current sensors...

Страница 19: ... 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 19 Sensor Securing mechanism for connecting the individual sensors in the sensor bar Cable entry for the power cable Connections for the sensor bar ...

Страница 20: ...asuring system 20 System Manual 11 2016 2514374103 02 3 3 Application area The system is used primarily in the following areas Small businesses Halls Residential buildings Supermarkets Data centers Office buildings Application example of a brewery Figure 3 1 Application example ...

Страница 21: ...tus Indicates readiness Status Readiness for operation Off Device switched off Orange Voltage boot active Green slow flashing Linux is booting Green rapid flashing Firmware update in progress Green continuous Device ON Table 3 2 Network Indicates connection with the supply system indicates supply system activ ity Status Readiness for operation Off LAN has no link Green on LAN has link Flashing gre...

Страница 22: ...ted via RS485 The sensor bar and the connected sensors are located on the individual fuses in the fuse cabinet Up to 8 sensor bars with 12 sensors each can be connected giving a total of 96 sensors in the maximum configuration The length of cable between the Data Manager and a maximum of 8 sensor bars must not exceed 10 meters The Data Manager is connected by LAN if necessary via an additional rou...

Страница 23: ...7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 23 Connection 4 TN system Line connection infeed Loads IT system Line connection infeed Loads ...

Страница 24: ...e Data Manager has a 63 A direct connection For applications with other requirements external current transformers can be additionally connected to the Data Manager The corresponding transformer ratio can be set in the web browser so that the accuracy is not impaired When using external current transformers the respective measuring accuracy must be taken into account The Data Manager displays the ...

Страница 25: ...ditional connection for N In the middle you will find the connection for the LAN cable The connection for the RS485 connector is at the top of the Data Manager Note if the communication cable is incorrectly connected the Data Manager switches to a protection mode and does not perform any measurements To trigger a reset you must briefly disconnect the Data Manager from the auxiliary power ...

Страница 26: ......

Страница 27: ...s are supported Microsoft Internet Explorer from version 8 Mozilla Firefox from version 17 Google Chrome from Version 21 Apple Safari from Version 6 Settings via the system environment The following settings can be made via the web interface Network Settings Settings for the network and the time server Data backup Create or restore data backups Firmware update Perform firmware update Reset Restart...

Страница 28: ...ing Time of day Language Network Settings Country Currency Tariff settings Budget Where applicable Transformer ratio Modbus settings and sensor management connection labeling phase assignment and grouping of the individual sensors 5 1 2 Function overview The browser based web application offers the following functions Statistics Current values Installment Energy stopwatch Settings ...

Страница 29: ...page opens Figure 5 1 Home The Start page shows the instantaneous consumption at the specified rate on the day Depending on the configuration consumption can be displayed per hour per day per week per month and per year If the product has not yet been operation for a year projections are displayed On the left hand side is a navigation bar via which you can access different sub menus Additional pro...

Страница 30: ...shown both in euros and in kWh The results can be displayed in the form of a pie chart or a bar chart depending on selection The periods that can be selected are as follows Days Week Months Year Both the overall consumption and the individual consumption of a sensor can be displayed It is also possible to generate a history so that any deviations can be investigated A date can be selected for this...

Страница 31: ... at a particular moment in time The Current value indicates this consumption Min Max indicates the minimum and maximum consumption The kW values consumed at a certain time are shown in a curve diagram Here also either the overall consumption or the consumption of an individual sensor can be displayed It is also possible to switch between various modes in this view History Current values for indivi...

Страница 32: ...Installment The installment is calculated from the specified budget over a specified time period and from the monthly base fee If the budget is exceeded the final amount appears against a red background and a warning is issued on the Home page If annual budget is selected a table and a graphic appear with the monthly consumption Figure 5 4 Installment Day ...

Страница 33: ...Operator control software 5 1 Browser based web application 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 33 Figure 5 5 Installment Year ...

Страница 34: ...AC1200 multichannel current measuring system 34 System Manual 11 2016 2514374103 02 5 1 7 Energy stopwatch Consumption over a specific period can be checked with the current stopwatch These measurements can be saved for comparison purposes Figure 5 6 Energy stopwatch ...

Страница 35: ...AC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 35 5 1 8 Settings 5 1 8 1 Start On the Settings homepage you will find an overview of the serial number firmware version and LAN MAC address of the device Figure 5 7 Settings Start page ...

Страница 36: ...374103 02 5 1 8 2 Device In the menu item Device Settings the following settings can be made Language Location Date Time of day Transformer ratio Password These settings appear on initial commissioning of the Data Manager Figure 5 8 Device settings 5 1 8 3 Sensors Under Sensor settings you will find two views Sensor settings Current values ...

Страница 37: ...automatically The sensors can be assigned individual names and they must be assigned to individual phases In special applications the power factor can also be defined manually If a sensor is not connected there is also no need for any phase assignment An eye symbol on the far right shows which sensors are to be compared with each other statistically This can be adapted individually Up to eight sen...

Страница 38: ...different phases Current values of the individual sensors 0 values against a red background indicate sensors through which no power is currently flowing values with a red background indicate sensors for which no phase assignment has been carried out In this way it is immediately apparent if there is a fault or if the sensors are not active This view hugely reduces the search effort for errors espe...

Страница 39: ... Network Settings a static IP address can be assigned manually The Data Manager is supplied with a fixed IP address 192 168 1 200 The Data Manager can also be assigned an individual name here In the Timeserver settings you can determine whether the Data Manager obtains the time automatically from the network via the server This is only possible if the Data Manager is connected to the network Figur...

Страница 40: ...nquiries This port and the IP address must be configured to establish a connection with the Data Manager Data export In the case of data export a CSV file is exported This contains the instantaneous overall consumption and the consumption of the individual sensors in and kWh To enable recording of the values of the individual sensors in the CSV file data transmission via Modbus must be activated a...

Страница 41: ...Operator control software 5 1 Browser based web application 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 41 Figure 5 11 Data export ...

Страница 42: ...saved and sent by email or stored on an FTP server over a specified period Here too there is the option of activating data logging which results in a CSV file being saved to the hard disk at a specific resolution In this file you will find total power overall consumption current voltage and power factor These data are also included divided according to the different phases and the individual senso...

Страница 43: ...rmware update can then be installed The Data Manager restarts automatically following installation and changes to the Start page Firmware updates can be found in Industry Online Support https support industry siemens com cs ww en ps 21681 See also Firmware Update https support industry siemens com cs ww en ps 21681 5 1 8 7 Tariff settings Edit tariff The following values can be processed under Tar...

Страница 44: ...1 Browser based web application 7KT PAC1200 multichannel current measuring system 44 System Manual 11 2016 2514374103 02 Figure 5 13 Tariff settings Adjust tariff Under Adjust tariff the tariff can be changed at a particular time ...

Страница 45: ...be used When calculating the installment the budget is distributed evenly across the number of months Figure 5 14 Budget settings 5 1 8 9 Reset There are three options under the menu item Reset Restart device Settings and other data are retained Reset configurations Network and sensor settings are deleted but the configuration of the Modbus data transfer is retained Reset device to the delivery st...

Страница 46: ...lication for mobile devices it must first be installed on the desired devices The procedure depends on the device used Android device Download the application from Google Play Store https play google com store apps details id de siemens homebox utm_source global_co utm_medium prtnr utm_content Mar2515 utm_campaign PartBadge pcampaignid MK T Other global all co prtnr py PartBadge Mar2515 1 iOS devi...

Страница 47: ... google com store apps details id de siemens homebox utm_source global_co utm_medium prtnr utm_content Mar2515 utm_campaign PartBadge pcampaignid MK T Other global all co prtnr py PartBadge Mar2515 1 iOS link https geo itunes apple com us app 7kt pac1200 id1091508286 mt 8 Android screen https play google com intl en_us badges images generic de play badge png iOS screen http linkmaker itunes apple ...

Страница 48: ...n selected the Home page showing the current energy consumption appears Further information on available on the Home page Date and time Navigation to Statistics Current values Installment Energy stopwatch Closing of the selected multichannel current measuring system Display returns to the selection of the detected systems Swipe to the left right to change between hourly daily weekly monthly and an...

Страница 49: ...Operator control software 5 2 Application for mobile devices 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 49 Figure 5 15 Start page of the application ...

Страница 50: ...50 System Manual 11 2016 2514374103 02 5 2 3 Statistics The Statistics view offers the following evaluations Overall consumption Individual system consumption Individual consumption Consumption of the individual sensors Consumption top right can be shown in kWh Possible display intervals Hour Day Week Month Year ...

Страница 51: ...ontrol software 5 2 Application for mobile devices 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 51 Overall consumption Overall consumption is visualized using a bar chart ...

Страница 52: ...ed here in a direct comparison Individual consumption In the case of individual consumption all selected sensors are represented underneath each other in a horizontal bar chart In this way the individual sensors can be compared at a glance This in turn means that differences in consumption of the individual sensors can be quickly detected All sensors connected to the Data Manager as well as in the...

Страница 53: ...System Manual 11 2016 2514374103 02 53 5 2 4 Current values The current values are represented in real time exactly as in the browser based web application It is possible to stop the recording here The latest current power values are also shown in the current values Figure 5 16 Current values Overall consumption ...

Страница 54: ...KT PAC1200 multichannel current measuring system 54 System Manual 11 2016 2514374103 02 Figure 5 17 Current values Current values Another method of accessing the Data Manager via the application is to use the energy stopwatch This can be started and stopped again ...

Страница 55: ... light up or the Data Manager is not found in the network Problem The network cable is not correctly connected to the network connection Solution Ensure that the network cable is correctly connected to the network connection Problem The Data Manager is not located in the same local network Solution Connect the Data Manager with the same router switch or change the IP address in the PC The Energy M...

Страница 56: ......

Страница 57: ...Modbus RTU Voltage and current inputs Rated voltage 230 400 V AC Operating voltage 230 V 10 Frequency 50 Hz 5 Intrinsic consumption Voltage circuit 0 01 VA per phase Current circuit 2 VA per phase Overall device 5 W Rated current 5 A Current limit 63 A Starting current 25 mA Mounting Conductor cross section 10 25 mm2 mechanically from 1 5 25 mm2 Torque for screw terminals 2 0 Nm ...

Страница 58: ...ve energy Class 1 Reactive energy Class 1 When using external current transformers the respective measuring accuracy must be taken into account EMC ESD IEC 61000 4 2 4 kV contact discharge 8 kV air discharge RF irradiation 3 V m Burst IEC 61000 4 4 Network 4 kV Ethernet 2 kV Surge IEC 61000 4 5 Phase phase 1 kV Phase ground 2 kV Ethernet 2 kV Conducted interference IEC 61000 4 6 150 kHz 80 MHz RMS...

Страница 59: ...ass fiber reinforced polyamide Glow wire test According to IEC 695 2 1 Protection class type II IP20 Weight size 0 3 kg 88x70x65 mm RS485 interface Protocol Modbus Type RS485 half duplex Data transmission rate 19200 or 115200 kbits Connectors 4 pin male connector 2 54 mm enclosure Proprietary RS 485 driver Slew rate limited CS Sensor MAX13412 Electrical isolation No Power supplies for sensors Yes ...

Страница 60: ...uring system 60 System Manual 11 2016 2514374103 02 Table 7 1 Connector assignments Pin direct Pin indirect Description 1 4 Supply voltage 9 V 2 3 RS485 B 3 2 RS485 A 4 1 Ground 7 1 Dimension drawings 7 1 1 Dimensions of the Data Manager View from the right and from the front ...

Страница 61: ...a 7 1 Dimension drawings 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 61 View from above and from below 7 1 2 Dimensions of the sensor bar Sensor bar with three sensor slots ...

Страница 62: ...Technical data 7 1 Dimension drawings 7KT PAC1200 multichannel current measuring system 62 System Manual 11 2016 2514374103 02 Sensor bar with six sensor slots ...

Страница 63: ...Technical data 7 1 Dimension drawings 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 63 Sensor bar with nine sensor slots ...

Страница 64: ...Technical data 7 1 Dimension drawings 7KT PAC1200 multichannel current measuring system 64 System Manual 11 2016 2514374103 02 Sensor bar with twelve sensor slots ...

Страница 65: ...Technical data 7 1 Dimension drawings 7KT PAC1200 multichannel current measuring system System Manual 11 2016 2514374103 02 65 7 1 3 Dimensions of the sensors on the sensor bar ...

Страница 66: ......

Страница 67: ...r 1 overall system 2 At which intervals are the sensor values transferred to Siemens Data Manager 1 second In which languages can the system be configured In German and English Is the actual current communicated by the sensors or only a ratio The current is measured in amperes Is mixed operation of 40 A and 63 A sensors possible in the case of the sensor bar It is possible ...

Страница 68: ...See 4 5 Sensor registers A 3 Internal registers Internal immediate registers Start address deci mal End address deci mal Start address hexa decimal End address hexa decimal Size R W Func tion codes Type Units OBIS code Description 0 1 0x0000 0x0001 2 RO 0x03 Unit 32 0 1 W 1 0 1 4 0 255 Active power 2 3 0x0002 0x0003 2 RO 0x03 Unit 32 0 1 W 1 0 2 4 0 255 Active power 4 5 0x0004 0x0005 2 RO 0x03 Uni...

Страница 69: ... 0 255 Reactive power L1 46 47 0x002E 0x002F 2 RO 0x03 Unit 32 0 1 var 1 0 24 4 0 255 Reactive power L1 48 49 0x0030 0x0031 2 RO 0x03 reserved 50 51 0x0032 0x0033 2 RO 0x03 reserved 52 53 0x0034 0x0035 2 RO 0x03 reserved 54 55 0x0036 0x0037 2 RO 0x03 reserved 56 57 0x0038 0x0039 2 RO 0x03 Unit 32 0 1 VA 1 0 29 4 0 255 Active power L1 58 59 0x003A 0x003B 2 RO 0x03 Unit 32 0 1 VA 1 0 30 4 0 255 Acti...

Страница 70: ... 0x03 reserved 110 111 0x006E 0x006F 2 RO 0x03 reserved 112 113 0x0070 0x0071 2 RO 0x03 reserved 114 115 0x0072 0x0073 2 RO 0x03 reserved 116 117 0x0074 0x0075 2 RO 0x03 reserved 118 119 0x0076 0x0077 2 RO 0x03 reserved 120 121 0x0078 0x0079 2 RO 0x03 Unit 32 0 1 W 1 0 61 4 0 255 Active power L3 122 123 0x007A 0x007B 2 RO 0x03 Unit 32 0 1 W 1 0 62 4 0 255 Active power L3 124 125 0x007C 0x007D 2 RO...

Страница 71: ... 548 551 0x0224 0x0227 4 RO 0x03 Unit 64 0 1 VAh 1 0 10 8 0 255 Apparent power 552 555 0x0228 0x022B 4 RO 0x03 reserved 556 559 0x022C 0x022F 4 RO 0x03 reserved 560 563 0x0230 0x0233 4 RO 0x03 reserved 564 567 0x0234 0x0237 4 RO 0x03 reserved 568 571 0x0238 0x023B 4 RO 0x03 reserved 572 575 0x023C 0x023F 4 RO 0x03 reserved 576 579 0x0240 0x0243 4 RO 0x03 reserved 580 583 0x0244 0x0247 4 RO 0x03 re...

Страница 72: ... varh 1 0 44 8 0 255 Reactive power L2 688 691 0x02B0 0x02B3 4 RO 0x03 reserved 692 695 0x02B4 0x02B7 4 RO 0x03 reserved 696 699 0x02B8 0x02BB 4 RO 0x03 reserved 700 703 0x02BC 0x02BF 4 RO 0x03 reserved 704 707 0x02C0 0x02C3 4 RO 0x03 Unit 64 0 1 VAh 1 0 49 8 0 255 Apparent power L2 708 711 0x02C4 0x02C7 4 RO 0x03 Unit 64 0 1 VAh 1 0 50 8 0 255 Apparent power L2 712 715 0x02C8 0x02CB 4 RO 0x03 res...

Страница 73: ...92 8192 0x2000 0x2000 1 RO 0x03 Unit 16 Manufac turer s ID 0x5233 Fixed value to identify each device 8193 8193 0x2001 0x2001 1 RO 0x03 Unit 16 Product ID 0x4842 Indicates that the device is a Data Man ager 8194 8194 0x2002 0x2002 1 RO 0x03 Unit 16 Product version Example 0x0200 2 00 Hardware revision of the Data Manager 8195 8195 0x2003 0x2003 1 RO 0x03 Unit 16 Firmware version Example 0x020D 525...

Страница 74: ...Series 16 N A N A Manufacturer specific value 40052 40067 16 RO 0x03 C_SerialN umber Series 16 N A N A Manufacturer specific value 40068 40068 1 RO 0x03 C_Device Address Unit 16 N A N A Modbus ID Modbus ad dress Indicates that it is valid 247 40069 40069 1 RO 0x03 C_SunSp ec_DID Unit 16 N A N A SunSpec meter model block 203 40070 40070 1 RO 0x03 C_SunSp ec_Length Unit 16 regis ters N A Length of t...

Страница 75: ...t potential 0x8000 40083 40083 1 RO 0x03 M_AC_Vol tage_CA Unit 16 V M_AC_Vol tage_SF Phase C to phase A AC current potential 0x8000 40084 40084 1 RO 0x03 M_AC_Vol tage_SF Unit 16 N A N A AC current po tential scaling factor 2 40085 40085 1 RO 0x03 M_AC_Fre q Unit 16 Hz M_AC_Fre q_SF AC frequency 1 0 14 4 0 255 40086 40086 1 RO 0x03 M_AC_Fre q_SF Unit 16 N A N A AC frequency scaling factor 2 40087 ...

Страница 76: ...SF Unit 16 N A N A AC apparent power scaling factor 1 40097 40097 1 RO 0x03 M_AC_VA R Unit 16 var M_AC_VA R_SF Total AC reac tive power total of active phas es 0 1 0 4 4 0 255 40098 40098 1 RO 0x03 M_AC_VA R_A Unit 16 var M_AC_VA R_SF Phase A AC reactive power 0 1 0 23 4 0 255 0 1 0 24 4 0 255 40099 40099 1 RO 0x03 M_AC_VA R_B Unit 16 var M_AC_VA R_SF Phase B AC reactive power 0 1 0 43 4 0 255 0 1...

Страница 77: ...21 8 0 255 40119 40120 2 RO 0x03 M_Importe d_B Unit 32 Wh M_Energy _W_SF Phase B import ed real energy 1 0 41 8 0 255 40121 40122 2 RO 0x03 M_Importe d_C Unit 32 Wh M_Energy _W_SF Phase C import ed real energy 1 0 61 8 0 255 40123 40123 1 RO 0x03 M_Energy _W_SF Unit 16 N A N A Real energy scaling factor 0 40124 40125 2 RO 0x03 M_Export ed_VA Unit 32 VAh M_Energy _VA_SF Total exported apparent ener...

Страница 78: ...ARh M_Energy _VAR_SF Phase B quad rant 2 imported reactive energy 0x80000000 40155 40156 2 RO 0x03 M_Import_ VARh_Q2 C Unit 32 VARh M_Energy _VAR_SF Phase C quad rant 2 imported reactive energy 0x80000000 40157 40158 2 RO 0x03 M_Export_ VARh_Q3 Unit 32 VARh M_Energy _VAR_SF Quadrant 3 total imported reactive energy 0x80000000 40159 40160 2 RO 0x03 M_Export_ VARh_Q3 A Unit 32 VARh M_Energy _VAR_SF ...

Страница 79: ...t flags indicates that it is valid 0 40176 40176 1 RO 0x03 C_SunSp ec_DID Unit 16 N A N A SunSpec end model block 0xffff 40177 40177 1 RO 0x03 C_SunSp ec_Length Unit 16 regis ters N A Length of end model 0 A 4 Sensor registers Overview Start address decimal End address decimal Start address hexadecimal End address hexadecimal Size Description 61440 61479 0xF000 0xF027 40 Sensor 1 61480 61519 0xF02...

Страница 80: ...ower cal culated 61453 61456 0xF00D 0xF010 4 RO 0x03 re served 61457 61460 0xF011 0xF014 4 RO 0x03 Unit 64 1 VAh 1 x 9 8 0 255 Apparent energy cal culated 61461 61464 0xF015 0xF018 4 RO 0x03 re served 61465 61466 0xF019 0xF01A 2 RO 0x03 Unit 32 0 001 W 1 x 1 4 0 255 Active power cal culated 61467 61468 0xF01B 0xF01C 2 RO 0x03 re served 61469 61470 0xF01D 0xF01E 2 RO 0x03 Unit 32 0 001 VA 1 x 9 4 0...

Страница 81: ...ur body electrostatically immediately before touching an electronic component To do this touch a conductive grounded object e g a bare metal part of a switch cabinet or the water pipe Always hold the component by the plastic enclosure Electronic modules should not be brought into contact with electrically insulating materials such as plastic film plastic parts insulating table supports or clothing...

Страница 82: ...multichannel current measuring system 82 System Manual 11 2016 2514374103 02 1 ESD seat 2 ESD standing position 3 ESD seat and ESD standing position Protective measures a Conductive floor b ESD table c ESD footwear d ESD smock e ESD bracelet f Cubicle ground connection ...

Страница 83: ...ructured data Spreadsheet programs such as Microsoft Excel can read in or export CSV files IT system Separation of all active parts from ground or connection between a point and ground via an impedance in the distribution system Direct grounding of the exposed conductive part of the electrical installation regardless of existing grounding of a point in the supply system Modbus One master and sever...

Страница 84: ......

Страница 85: ...tatistics 30 System environment 27 Tariff settings 43 Budget Settings 45 C Conductive floor 82 Connection 23 25 Cubicle ground connection 82 Current values 31 Application 53 D Data export Settings 40 Data Manager Dimensions 60 Introduction 15 Overview 16 Device Settings 36 Diagnostics option LEDs 21 Network LED 21 Sensor LED 22 Status LED 21 Dimensions Data Manager 60 Sensor bar 61 Discharge 81 Di...

Страница 86: ...rview 19 Settings 37 Sensor bar Dimensions 61 Overview 18 Settings Background information 35 Browser application 35 Budget 45 Data export 40 Device 36 Network 39 Reset 45 Sensor 37 Start up 28 System environment 27 Tariff 43 Start up Settings 28 Statistics 30 Application 50 Storage 81 System environment 22 Browser application 27 Settings 27 T Tariff Settings 43 Technical specifications 57 Intrinsi...

Страница 87: ......

Страница 88: ...ge Products Postfach 10 09 53 93009 REGENSBURG GERMANY Subject to change 3ZW1012 0KT12 0AC1 Siemens AG 2016 LV Explorer Discover Low Voltage in 3D www siemens com lowvoltage lv explorer Always at your disposal our extensive support www siemens com lowvoltage support ...

Отзывы: