7KT PAC1200 multichannel current measuring system
System Manual, 11/2016, 2514374103-02
57
Technical data
7
Interfaces (standard)
●
LAN (10 / 100 Mbits)
●
RS485 for data transfer by means of Modbus RTU
Voltage and current inputs
Rated voltage
230 / 400 V AC
Operating voltage
230 V ± 10 %
Frequency
50 Hz ± 5 %
Intrinsic consumption
Voltage circuit
< 0.01 VA per phase
Current circuit
< 2 VA per phase
Overall device
< 5 W
Rated current
5 A
Current limit
63 A
Starting current
< 25 mA
Mounting
Conductor cross-section
10 ... 25 mm
2
(mechanically from
1.5 ... 25 mm
2
)
Torque for screw terminals
2.0 Nm