Procedure
1. Place the trapeze nut into the suspension rail, feed the trapeze spindle of the weighing device through the
hole in the suspension rail and screw the slightly greased trapeze spindle into the trapeze nut until it appears
at the end of the nut.
2. Secure the two trapeze nuts at the lower end of the spindle to each other (counter).
3. Bring the two thread rods (M10) into the weighing device and secure them flush in the 2 hut nuts.
4. Screw the neck ring onto the cylinder, orientating the slots with respect to the cylinder valve (in line with the
burst disc port) and locate the threaded rods of the weighing device into the slots on the neck ring
5. Turn the lower counter nut anti-clockwise. The cylinder is lifted up. Continue to turn it until the cylinder hangs
at least 2 cm above the floor. The cylinder can lifted up so high, that it is possible to place periodically a
external weighing device to check the filling quantity. It is also possible to lift up the cylinders with the CO2
weighing device tool S54476-B157-A15 with on site portable electrical drill with wrench AF/ SW30.
6. Align the weighing device trip mechanism and weight spindle so that they are parallel to the suspension rail.
7. Adjust the height of the cylinders so that the valve outlet ports are all at the same height.
8. Open the two counter nuts from each other and secure them at the lower and upper end of the trapeze
spindle to prevent the weighing device from being rotated
9. Remove the Tommy bar. The device with the fixed cylinder is now ready to adjust.
10. Replace of cylinder f.e. after a release same procedure in opposite way
Assembly instructions electrical remote indication switch
The weighing device is supplied with a bracket and trip plate fitted.
There is type of remote indication switch (optional).
·
Siemens CX 1562010 / A5Q00032144 including all fixations, documentation 12-01-010
Technische Daten / Technical data
Deutsch
English
Endschalter
position switch
Siemens
CX Artikelnummer
CX ref.no.
1562010
SAP
SAP
A5Q00032144
Typ
type
3SE5 232-OHC05
Kabel
cable
nein / no
Kabel Zugentlastung
cable strainrelief
ja / yes
Schaltanschluss
connection
1 NO + 1NC
Kapselung
closure
gekapselt / enclosed
Anschluss
connection
48V, 1A, IP65
Konformitätserklärung
EC Declaration of Conformity
2011/65/EU
Remote indication switches must be fixed to the bracket as follows:
Deutsch
English
Schraube
screw
2 x CX 507053 / A5Q00032190 M4x35
Mutter
screw nut
2 x CX 180377 / A5Q00032183 M4
The cable connection is fitted via:
Deutsch
English
Kabelverschraubung M20x1.5
cable screw connection m20x1.5
1 x A5Q00031978
Switch and switch cable connection material are part of
S54476-S45-A1 / S54476-S45-A2.
bracket