Siemens SBT WD2005 Скачать руководство пользователя страница 3

3/6

Building Technologies

02-01-900 E.doc

Fire Safety & Security Products

Schmersal

Siemens

Procedure

1.  Place the trapeze nut into the suspension rail, feed the trapeze spindle of the weighing device through the

hole in the suspension rail and screw the slightly greased trapeze spindle into the trapeze nut until it appears
at the end of the nut.

2.  Secure the two trapeze nuts at the lower end of the spindle to each other (counter).
3.  Bring the two thread rods (M10) into the weighing device and secure them flush in the 2 hut nuts.
4.  Screw the neck ring onto the cylinder, orientating the slots with respect to the cylinder valve (in line with the

burst disc port) and locate the threaded rods of the weighing device into the slots on the neck ring

5.  Turn the lower counter nut anti-clockwise. The cylinder is lifted up. Continue to turn it until the cylinder hangs

at least 2 cm above the floor. The cylinder can lifted up so high, that it is possible to place periodically a
external weighing device to check the filling quantity. It is also possible to lift up the cylinders with the CO2
weighing device tool S54476-B157-A15 with on site portable electrical drill with wrench AF/ SW30.

6.  Align the weighing device trip mechanism and weight spindle so that they are parallel to the suspension rail.
7.  Adjust the height of the cylinders so that the valve outlet ports are all at the same height.
8.  Open the two counter nuts from each other and secure them at the lower and upper end of the trapeze

spindle  to prevent the weighing device from being rotated

9.  Remove the Tommy bar. The device with the fixed cylinder is now ready to adjust.
10.  Replace of cylinder f.e. after a release same procedure in opposite way

Assembly instructions electrical remote indication switch

The weighing device is supplied with a bracket and trip plate fitted.

There is type of remote indication switch (optional).

·

 

Siemens CX 1562010 / A5Q00032144 including all fixations, documentation 12-01-010

Technische Daten / Technical data

Deutsch

English

Endschalter

position switch

Siemens

CX Artikelnummer

CX ref.no.

1562010

SAP

SAP

A5Q00032144

Typ

type

3SE5 232-OHC05

Kabel

cable

nein / no

Kabel Zugentlastung

cable strainrelief

ja / yes

Schaltanschluss

connection

1 NO + 1NC

Kapselung

closure

gekapselt / enclosed

Anschluss

connection

48V, 1A, IP65

Konformitätserklärung

EC Declaration of Conformity

2011/65/EU

Remote indication switches must be fixed to the bracket as follows:

Deutsch

English

Schraube

screw

2 x CX 507053 / A5Q00032190 M4x35

Mutter

screw nut

2 x CX 180377 / A5Q00032183 M4

The cable connection is fitted via:

Deutsch

English

Kabelverschraubung M20x1.5

cable screw connection m20x1.5

1 x A5Q00031978

Switch and switch cable connection material are part of

S54476-S45-A1 / S54476-S45-A2.

bracket

Содержание SBT WD2005

Страница 1: ...r Technical data material galvanized steel working temperature 0 50 C max humidity 70 max gross load 200 kg max net load 96kg min net load 10kg mass loss indication supervision electrical with pos switch mass loss indication supervision with counterweights available counterweights 250g CX560250 500g CX560500 1000g CX561000 1500g CX561500 2000g CX562000 S54476 B52 A1 S54476 B52 A2 S54476 B52 A3 S54...

Страница 2: ...Assembly sleeve with tommy bar tool Pos 4 Lock nut Pos 5 Drilled hole Pos 6 Threaded rods Pos 7 Neck ring Pos 8 Trip mechanism Pos 9 Suspension rail Pos 10 Balance weights Pos 11 Weight spindle and nuts Pos 12 Cylinder Assembly instructions On site addition of fixation with of M10 nut will prevent from hanging out thread rod and neck ring ...

Страница 3: ...spension rail 7 Adjust the height of the cylinders so that the valve outlet ports are all at the same height 8 Open the two counter nuts from each other and secure them at the lower and upper end of the trapeze spindle to prevent the weighing device from being rotated 9 Remove the Tommy bar The device with the fixed cylinder is now ready to adjust 10 Replace of cylinder f e after a release same pr...

Страница 4: ... 80 4 kg bis 1 2 170 10 kg Fk 5 1 12 80L 32 kg von 0 4 125 5 kg Fk 5 1 12 80L 96 kg bis 1 2 190 10 kg HFC 227 67L 26 8 kg von 0 4 115 5 kg HFC 227 67L 67 kg bis 1 0 155 10 kg HFC 227 80L 32 kg von 0 4 125 5 kg HFC 227 80L 80 kg bis 1 0 175 10 kg Gross load Balance weight table Number of turns Balanced position Selfholding position 25 5kg 250g 0 4 60kg 500 250g 0 75 86kg 1000g 1 90kg 1000g 1 95kg 1...

Страница 5: ... on the weight spindle until the weight spindle remains in the balanced position pos 2 3 From this position rotate the Balance weight s clockwise by the number of turns specified in the table for the size and fill weight of the cylinder Fit a nut to the weight spindle and tighten onto the weight s to secure in position Option check with a butcher spring balance range 0 5kg The weighing device move...

Страница 6: ...echanism is evident shall be replaced Ensure all lock nuts are tight The correct setting of the weighing device can be verified using a flat bar 300mm to 500mm length and small pivot 25mm 50mm section steel angle or diameter round bar Place the flat bar onto the ground so that one end of the bar is approximately 50mm under the base of the cylinder Place the pivot under the middle of the flat bar a...