Siemens SBT WD2005 Скачать руководство пользователя страница 1

1/6

Building Technologies

02-01-900 E.doc

Fire Safety & Security Products

Weighing device for indicating loss of a critical mass of extinguishant

ENGLISH

02-01-900

PED-category:

Weighing Device SBT WD2005

WD2005-67 / WD2005-80

Index  Description

Date

Fluid group:

01.10.06

Product line

Sinorix ™

b

adjusting procedure

27.08.10

c

Set, tool new

01.05.14

CX ref. no.

560000

d

RoHS, CO2 80L

01.12.15

e

NO / NC, CO2 80L

01.03.18

G305001

0786CPR30044

SAP

S54476-B45-A1

EN 12094-11

589

2

83

220

52

The weighing device SBT WD2005 by

SIEMENS

 indicates the loss of a critical mass

of

extinguishant from the

cylinders.
The weighing device set consists of weighing device plus counterweight depending of the cylinder volume.

S54476-S45-A1 = S54476-B45-A1 + S54476-B52-A4

(counterweight 1.5 kg for 67 L)

S54476-S45-A2 = S54476-B45-A1 + S54476-B52-A5

(counterweight 2.0 kg for 80 L)

If the weighing device is to be used outdoors, it must be protected against the ingress of water.

Technical data

material

galvanized steel

working temperature

0 … 50° C

max. humidity

70%

max. gross load

200 kg

max. net load

   96kg

min. net load

   10kg

mass loss indication supervision

electrical with pos. switch

mass loss indication supervision

with counterweights

available counterweights

250g (CX560250), 500g (CX560500), 1000g (CX561000), 1500g (CX561500), 2000g (CX562000)
S54476-B52-A1, S54476-B52-A2, S54476-B52-A3, S54476-B52-A4, S54476-B52-A5

mass loss indication

adjustible 5% - 10%

Operating Principle

The weighing device operates on the principle of an eccentric pivot.
An adjustable position balance weight mounted on the weight spindle enables the device to be set to indicate
the mass loss over a range of gross loads. If the cylinder weight and the balancing weight are equal, the
system is stable (balance weight is in the horizontal ‘set’ position). If the net weight reduces (due to leakage
from the cylinder) the balance weight drops downwards (balance weight moves to the inclined ‘tripped’
position). The weighing device is adjusted to indicate a loss of mass of 5% from the suspended cylinder.

The weighing device must be reset manually to resume its function.

Содержание SBT WD2005

Страница 1: ...r Technical data material galvanized steel working temperature 0 50 C max humidity 70 max gross load 200 kg max net load 96kg min net load 10kg mass loss indication supervision electrical with pos switch mass loss indication supervision with counterweights available counterweights 250g CX560250 500g CX560500 1000g CX561000 1500g CX561500 2000g CX562000 S54476 B52 A1 S54476 B52 A2 S54476 B52 A3 S54...

Страница 2: ...Assembly sleeve with tommy bar tool Pos 4 Lock nut Pos 5 Drilled hole Pos 6 Threaded rods Pos 7 Neck ring Pos 8 Trip mechanism Pos 9 Suspension rail Pos 10 Balance weights Pos 11 Weight spindle and nuts Pos 12 Cylinder Assembly instructions On site addition of fixation with of M10 nut will prevent from hanging out thread rod and neck ring ...

Страница 3: ...spension rail 7 Adjust the height of the cylinders so that the valve outlet ports are all at the same height 8 Open the two counter nuts from each other and secure them at the lower and upper end of the trapeze spindle to prevent the weighing device from being rotated 9 Remove the Tommy bar The device with the fixed cylinder is now ready to adjust 10 Replace of cylinder f e after a release same pr...

Страница 4: ... 80 4 kg bis 1 2 170 10 kg Fk 5 1 12 80L 32 kg von 0 4 125 5 kg Fk 5 1 12 80L 96 kg bis 1 2 190 10 kg HFC 227 67L 26 8 kg von 0 4 115 5 kg HFC 227 67L 67 kg bis 1 0 155 10 kg HFC 227 80L 32 kg von 0 4 125 5 kg HFC 227 80L 80 kg bis 1 0 175 10 kg Gross load Balance weight table Number of turns Balanced position Selfholding position 25 5kg 250g 0 4 60kg 500 250g 0 75 86kg 1000g 1 90kg 1000g 1 95kg 1...

Страница 5: ... on the weight spindle until the weight spindle remains in the balanced position pos 2 3 From this position rotate the Balance weight s clockwise by the number of turns specified in the table for the size and fill weight of the cylinder Fit a nut to the weight spindle and tighten onto the weight s to secure in position Option check with a butcher spring balance range 0 5kg The weighing device move...

Страница 6: ...echanism is evident shall be replaced Ensure all lock nuts are tight The correct setting of the weighing device can be verified using a flat bar 300mm to 500mm length and small pivot 25mm 50mm section steel angle or diameter round bar Place the flat bar onto the ground so that one end of the bar is approximately 50mm under the base of the cylinder Place the pivot under the middle of the flat bar a...