Siemens Building Technologies / Landis & Staefa Division
CM2G3368X1
14.02.00
9
it
Procedura di Set Up
se è impiegato l‘ingresso digitale
A
B
C
D
33
68
F
0
1
E
SETUP
MODE
Set Digital
Input
PI/P
on
2nd Input
on
Select "on"
Select "on"
Select "off"
Select "off"
Set Mode
On-Off or 3 Pos
A
B
33
68
F
0
3
E
Set Summer Set
Temperature
Summer/Winter
*
Day/Night
Set Winter Set
Temperature
Set Night Set
Temperature
Set Day Set
Temperature
SW or DN
*
Se l‘USCITA 2 = Off
l‘USCITA 1 può essere invertita (commutazione Summer/Winter)
se viene impiegato il secondo ingresso analogico
33
68
F
0
2
E
yes
no
Set SD1
Set XDZ
END
O/P1
Yes
Set OP1
heat/cool
Set O/P2
heat/cool/off
ON-OFF
Set Output 1
heat or cool
Set O/P2
cool/off
O/P2 is
heat or cool
Set SD2
Set TN
Set XP
Set TCYC
No-3 position
cool
heat
D
C
33
68
F
0
4
E
PI
Limiter
Set Limiting
Temperature
up/down
up/down
Set Min. or Max.
up/down
Remote
Setpoint
Temp.
Difference
Temp.
Shift
Set Range Scale
Set Shift
Temperature
Set Unshifted
Temperature
Set Shift
End Temp.
Set Shift
Start Temp.
up/down