92/106
Siemens
Basic Documentation RVP360
CE1P2546en
Building Technologies
20 Communication
2017-07-24
If 1 (slave without remote control) is entered on the controller’s operating line 178
("Source of time of day"), the time of day on the QAW70 cannot be readjusted.
Op. line
QAW70
Function, parameter
Impact on controller, notes
1
Setpoint for NORMAL heat-
ing
Changes controller operating line 1
2
Setpoint for REDUCED
heating
Changes controller operating line 2
3
D.h.w. temperature setpoint Changes controller operating line 26 with
plant types providing d.h.w. heating
4
Weekday (entry of heating
program)
Corresponds to controller operating line 4
5
1. 1st heating phase, start
of NORMAL heating
Changes controller operating line 5
6
1. 1st heating phase, end
of NORMAL heating
Changes controller operating line 6
7
2. 2nd heating phase, start
of NORMAL heating
Changes controller operating line 7
8
2. 2nd heating phase, end
of NORMAL heating
Changes controller operating line 8
9
3. 3rd heating phase, start
of NORMAL heating
Changes controller operating line 9
10
3. 3rd heating phase, end
of NORMAL heating
Changes controller operating line 10
11
Display of weekdays 1...7 Cannot be changed (refer to chapter 7.3
12
Entry of time of day
Changes controller operating line 38
13
Display of d.h.w. tempera-
ture
Only with plant types providing d.h.w.
heating
14
Display of boiler tempera-
ture
(Only with plant types 5 - x and 6 - x)
15
Display of flow temperature
16
Holidays
Controller switches to protection mode
17
Reset to default values
QAW70 default entries apply
51
Bus address
For heating circuit 1, address 1 must
be entered
For heating circuit 2, address 2 must
be entered
52
Identification of room unit
53
Operating lock on QAW70 No impact on the controller
58
Type of setpoint display
No impact on the controller
Impact of the individual
QAW70 operating lines
on the controller