10/106
Siemens
Basic Documentation RVP360
CE1P2546en
Building Technologies
1 Summary
2017-07-24
For the room temperature:
Suitable are sensors operating with a sensing element LG-Ni1000:
Room sensor QAA24
For the outside temperature:
Outside sensor QAC22 (sensing element LG-Ni1000)
Outside sensor QAC32 (sensing element NTC 575)
The controllers identify automatically the type of sensor used.
1.3.2 Suitable room units
Room unit QAA50.110/101 for heating circuits 1 and 2
Room unit QAW70 for heating circuits 1 and 2
1.3.3 Suitable
actuators
The following types of actuators from Siemens can be used:
Electromotoric or electrohydraulic 3-position actuators with a running time of
30...873 seconds
2-position actuators
Operating voltage AC 24...230 V
1.3.4 Communication
The RVP360 is capable of communicating with …
all types of LPB-compatible controllers supplied by Siemens,
the SYNERGYR central unit OZW30 (software version 3.0 or higher).
1.3.5 Documentation
Type of document
Document no.
Stock no.
Data Sheet RVP360
N2546
STEP Web Client
Installation Instructions RVP360
(de, en, fr, it, nl, es, el, and ru)
G2546
74 319 0817 0
Operating Instructions RVP360
(de, en, fr, it, nl, es, el, and ru)
B2546
74 319 0818 0
CE Declaration of Conformity
T2545
STEP Web Client
Environmental Declaration
E2545
STEP Web Client
LPB Basic System Data
N2030
STEP Web Client
LPB Basic Engineering Data
N2032
STEP Web Client