10 Function block: Pump heating circuit
2017-07-24
10 Function block: Pump heating circuit
This function block ensures protection against overtemperatures in the pump heat-
ing circuit.
10.1 Operating line
Line Function, parameter
Factory setting
(range)
Unit
Heating
circuit
75
Overtemperature protection for the pump heating circuit
1 (0 / 1)
-
1
10.2 Protection against overtemperatures
The flow temperature can be higher than the temperature called for by the pump
heating circuit. This is the case when some other consumer (heating circuit 2 or
some other heating zone) generates a higher flow temperature setpoint than the
pump heating circuit.
The controller offsets the surplus energy by letting the heating circuit pump cycle,
thus preventing the pump heating circuit from overheating.
The pump’s cycling time is fixed at 10 minutes. The on time is calculated as fol-
lows:
T
Vw
T
Rw
= ––––––––––––
*
10 [min]
T
Kx
T
Rw
On time in minutes
T
Rw
Room temperature setpoint
T
Vw
Flow temperature setpoint
T
Kx
Boiler temperature
The on time of the heating circuit pump is limited as follows:
The pump’s minimum on time is 3 minutes
If the calculated on time exceeds 8 minutes, the pump runs continuously