background image

Communication Ports
4.3.2 Configuration and Setup

4.3.2

Configuration and Setup

If the RUGGEDCOM RS910L and another device both have Universal EoVDSL ports,

configure one device to be the Master and the other the Slave. If both devices have a

Long-Reach EoVDSL port, no Master/Slave configuration is necessary, since the ports

will already be fixed as Master or Slave.
Once configured and connected together, each device will attempt to achieve the

maximum speed based on the line length and conditions. The RUGGEDCOM RS910L's

Link/Act

 LED may flash on and off several times before setting on a final link speed

and declaring the port up.
For more information about configuring the RUGGEDCOM RS910L , refer to the 

RUGGEDCOM RS910L User Guide

 for the .

4.3.3

EoVDSL Performance

The following describes the behavior and performance characteristics of EoVDSL.

EoVDSL Modes

The EoVDSL port can be configured to operate in one of two modes:

Auto Mode (default)

In Auto Mode, the device will step through the different speeds and automatical-

ly select the best bit-rate based on the current line conditions.

Manual Mode

In Manual Mode, the user can select one of the speed settings and the device will

only attempt to attain the set speed.

If the line conditions degrade (reducing the SNR or Signal to Noise Ratio), but the de-

vice is able to maintain the link, an alarm will be triggered to notify the user of the

reduced SNR. By configuring the 

Rescan Mode

 parameter in RUGGEDCOM RS910L,

the user can control at which point the scan process will be restarted when the line

conditions degrade. If 

Link only

 is selected, the device will restart the scan process

if the line conditions degrade, such that the device is unable to maintain the current

link. If 

Link or SNR

 is selected, the device will restart the scan process if either the

SNR has dropped below a pre-defined acceptable level or when the device is unable

to maintain the current link, or whichever comes first.

Note

If the 

Mode

 parameter is set to 

Manual Mode

, the restart of the scan process will on-

ly attempt to attain the set speed in manual mode.

For information about configuring EoVDSL, refer to the 

 RUGGEDCOM RS910L User

Guide for the RUGGEDCOM RS910L 

.

26

RUGGEDCOM RS910L

Installation Manual, 02/2020, C79000-G8976-1030-06

Содержание RUGGEDCOM RS910L

Страница 1: ...Edition 02 2020 Installation Manual SIMATIC NET Rugged Ethernet Switches RUGGEDCOM RS910L https www siemens com ...

Страница 2: ...ed Ethernet Switches RUGGEDCOM RS910L Installation Manual Preface Introduction 1 Installing the Device 2 Device Management 3 Communication Ports 4 Technical Specifications 5 Certification 6 02 2020 C79000 G8976 1030 06 ...

Страница 3: ... personnel are those who based on their training and experience are capable of identify ing risks and avoiding potential hazards when working with these products systems Proper Use of Siemens Products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufactur...

Страница 4: ...vice in Hazardous Locations 8 2 3 Mounting the Device 9 2 3 1 Mounting the Device on a DIN Rail 9 2 3 2 Mounting the Device to a Panel 11 2 4 Connecting the Failsafe Alarm Relay 12 2 5 Connecting Power 13 2 5 1 Connecting High AC DC Power 14 2 5 2 Connecting Low DC Power 16 3 Device Management 19 3 1 Connecting to the Device 19 3 2 Configuring the Device 20 4 Communication Ports 21 4 1 Copper Ethe...

Страница 5: ...Port Specifications 31 5 6 Serial Port Specifications 32 5 7 Operating Environment 32 5 8 Mechanical Specifications 33 5 9 Dimension Drawings 33 6 Certification 35 6 1 Approvals 35 6 1 1 CSA 35 6 1 2 FCC 36 6 1 3 FDA CDRH 36 6 1 4 ISED 36 6 1 5 TÜV SÜD 36 6 1 6 RoHS 37 6 1 7 Other Approvals 37 6 2 EMC and Environmental Type Tests 37 iv RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030...

Страница 6: ...ilable online at https support industry siemens com To request or inquire about a user document con tact Siemens Customer Support Disclaimer of Liability Siemens has verified the contents of this document against the hardware and or soft ware described However deviations between the product and the documentation may exist Siemens shall not be liable for any errors or omissions contained herein or ...

Страница 7: ...on about training services and course availability visit https www siemens com or contact a Siemens Sales representative Customer Support Customer support is available 24 hours 7 days a week for all Siemens customers For technical support or general information contact Siemens Customer Support through any of the following methods Online Visit http www siemens com automation support request to subm...

Страница 8: ...try Sector 300 Applewood Crescent Concord Ontario Canada L4K 5C7 Telephone Toll free 1 888 264 0006 Tel 1 905 856 5288 Fax 1 905 856 1995 E Mail ruggedcom info i ia siemens com Web https www siemens com RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 vii ...

Страница 9: ...Preface Contacting Siemens viii RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 ...

Страница 10: ...d on plant floors and curb side traffic control cabinets An operating temperature range of 40 to 85 C 40 to 185 F coupled with hazardous location certification Class I Division 2 op tional conformal coating and a galvanized steel enclosure allows the RUGGEDCOM RS910L to be placed in almost any location The RUGGEDCOM RS910L can be mounted on a DIN rail or panel for efficient use of cabinet space Th...

Страница 11: ...g temperature no fans 20 AWG Galvanized Steel DIN or panel mounting options provide secure mechanical reliability Optional Conformal coated printed circuit boards Universal Power Supply Options Fully integrated power supply Universal high voltage range 125 250 VDC or 100 240 VAC Hazardous Environments 88 300 VDC or 85 264 VAC Non Hazardous Environments Dual low voltage DC inputs 24 or 48 VDC Termi...

Страница 12: ...evice via the serial console port refer to Connect ing to the Device Page 19 Communication Ports Communication ports in general receive and transmit data as well as provide access to the RUGGEDCOM RUGGEDCOM RS910L Web in terface For more information about the various ports available re fer to Communication Ports Page 21 Failsafe Alarm Relay Latches to default state when a power disruption or other...

Страница 13: ...e by a third party make sure it has been fully decommissioned For more information refer to the associated Configuration Manual Recycling and Disposal For environmentally friendly recycling and disposal of this device and related acces sories contact a facility certified to dispose of waste electrical and electronic equip ment Recycling and disposal must be done in accordance with local regulation...

Страница 14: ...ditions Distance m Cable Type Wavelength nm Modal Band width MHz km 100Base FX 1000Base SX 10GBase SR 850 200 275 33 OM1 62 5 125 1300 500 2000 850 500 550 82 OM2 50 125 1300 500 2000 850 1500 550 300 OM3 50 125 a 1300 500 2000 850 3500 550 400 OM4 50 125 a 1300 500 2000 a Laser optimized RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 5 ...

Страница 15: ...Introduction 1 5 1 Supported Fiber Optic Cables 6 RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 ...

Страница 16: ...T This product contains no user serviceable parts Attempted service by unauthorized personnel shall render all warranties null and void Changes or modifications not expressly approved by Siemens AG could invalidate specifications test results and agency approvals and void the user s authority to operate the equipment IMPORTANT This product should be installed in a restricted access location where ...

Страница 17: ... that is considered to be not accessible in normal operation without the use of a tool providing a degree of protection of not less than IP54 The enclosure should have a minimum service temperature range of 40 to 100 C 40 to 212 F The equipment should be used in an area of not more than pollution degree 2 The console port should only be used in the safe area The equipment should be appropriately c...

Страница 18: ...ional airflow Forced airflow is not required However any increase in airflow will result in a reduc tion of ambient temperature and improve the long term reliability of all equipment mounted in the rack space Note For detailed dimensions of the device with either DIN rail or panel hardware installed refer to Dimension Drawings Page 33 2 3 1 Mounting the Device on a DIN Rail The RUGGEDCOM RS910L ca...

Страница 19: ...liding release with a slot at the bottom for a flathead screwdriver 1 2 3 2 1 1 1 DIN Rail 2 DIN Rail Adapter Figure 2 1 Mounting the Device to a DIN Rail 2 Insert a flathead screwdriver into the slot of the sliding release and move it down 3 Push the device against the bottom of the DIN rail then let go of the sliding re lease to latch the device 10 RUGGEDCOM RS910L Installation Manual 02 2020 C7...

Страница 20: ...l 2 Swing the bottom of the device away from the DIN rail 3 Lift the device off the DIN rail 2 3 2 Mounting the Device to a Panel For panel installations the RUGGEDCOM RS910L can be equipped with panel adapters on the top and bottom of the chassis The adapters allow the device to be attached to a panel using screws To mount the device to a panel do the following 1 Prepare mounting holes in the pan...

Страница 21: ...d and there are no ac tive alarms If the device is not powered or if an active alarm is configured the relay opens the NO contact and closes the NC Normally Closed contact Note Control of the failsafe relay output is configurable through RUGGEDCOM RS910L One common application for this relay is to signal an alarm if a power failure occurs For more information refer to the RUGGEDCOM RS910L User Gui...

Страница 22: ...led For 125 250 VDC rated equipment an appropriately rated DC circuit breaker must be installed Use minimum 16 gage copper wiring when connecting terminal blocks Equipment must be installed according to applicable local wiring codes and standards All line to ground transient energy is shunted to the Surge Ground terminal In cases where users require the inputs to be isolated from ground remove the...

Страница 23: ...l hazard risk of damage to equipment Before testing the dielectric strength HIPOT in the field remove the braided ground cable connected to the surge ground terminal and chassis ground This cable connects transient suppression circuitry to chassis ground and must be removed in order to avoid damage to transient suppression circuitry during testing Note Torque all terminal connections to 0 6 N m 5 ...

Страница 24: ...om the power source to the positive live L termi nal on the terminal block 4 1 2 3 1 Positive Live L Terminal 2 Negative Neutral N Terminal 3 Surge Ground Terminal 4 Braided Ground Cable Figure 2 5 Terminal Block Wiring RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 15 ...

Страница 25: ...om the power source to the chassis groun terminal on the terminal block 2 5 2 Connecting Low DC Power RUGGEDCOM RS910L s equipped with 24 or 48 V power supply inputs feature reverse polarity protection and dual power supply inputs allowing the device to accept re dundant connections to a single DC power supply To connect a low DC power supply to the device do the following Note Torque all terminal...

Страница 26: ...erminal block 1 3 2 4 1 Positive Terminal 2 Negative Terminal 3 Surge Ground Terminal 4 Braided Ground Cable Figure 2 7 Terminal Block Wiring Single DC Power Supply Inputs 3 Connect the negative wire from the power source to the negative terminal on the terminal block RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 17 ...

Страница 27: ... Terminal Block Wiring Dual DC Power Supply Inputs 5 Using a braided wire or other appropriate grounding wire connect the surge ground terminal to the chassis ground connection The surge ground terminal is used as the ground conductor for all surge and transient suppression circuitry in ternal to the unit 6 Connect the ground wire from the power source to the chassis groun terminal on the terminal...

Страница 28: ...nergized Console Port Connect a workstation directly to the RS232 serial console port to access the boot time control and RUGGEDCOM RS910L console interface The console port provides access to RUGGEDCOM RS910L s console interface IMPORTANT The serial console port is intended to be used only as a temporary connection during initial configuration or troubleshooting and should only be used in a safe ...

Страница 29: ...net Ports Connect any of the available Ethernet ports on the device to a management switch and access the RUGGEDCOM RS910L console and Web interfaces via the device s IP address The factory default IP address for the RUGGEDCOM RS910L is https 192 168 0 1 For more information about available ports refer to Communication Ports Page 21 3 2 Configuring the Device Once the device is installed and conne...

Страница 30: ...ssignment Port Type 1 and 2 Serial Ports 3 and 4 Copper 10 100Base TX or Fiber Optic 100Base FX Ethernet Ports 9 EoVDSL Port 4 1 Copper Ethernet Ports The RUGGEDCOM RS910L supports multiple 10 100Base TX Ethernet ports that allow connection to standard Category 5 CAT 5 shielded or unshielded twisted pair cables with RJ45 male connectors RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 103...

Страница 31: ...y LED Figure 4 2 RJ45 Port LEDs LED State Description Yellow The port is op erating at 100 Mbps Speed Off The port is op erating at 10 Mbps Yellow Solid Link estab lished Yellow Blink ing Link activity Link Activity Off No link detect ed Pin Out The following is the pin out for the RJ45 male connectors 1 8 Figure 4 3 RJ45 Ethernet Port Pin Config uration Pin Name Description 1 RX Receive Data 2 RX...

Страница 32: ... Figure 4 5 LC Port 2 1 1 Tx Connector 2 Rx Connector Figure 4 6 SC Port 2 1 1 Tx Connector 2 Rx Connector Figure 4 7 ST Port LEDs Each port features an LED that indicates the link activity state of the port State Description Yellow Solid Link established Yellow Blinking Link activity Off No link detected Specifications For specifications on the available fiber optic Ethernet ports refer to Fiber ...

Страница 33: ...uishable from each other However the port type can be determined either from the order code or through the RUGGEDCOM RS910L user interface EoVDSL ports can be connected using RJ11 male connectors IMPORTANT Universal and Long Reach EoVDSL ports master or slave must be connected to EoVDSL ports slave or master of the same type Connection between Universal EoVDSL ports and Long Reach EoVDSL ports is ...

Страница 34: ... way of reducing both magnetic and capacitive in terference as they reduce the magnetic loop area to nearly zero and maintain a consistent distribution of capacitances to both ground and other sources There fore make sure twisting is consistent throughout the cable length Open leads also known as bridged taps or drop lines along the length of the ca ble will cause an impedance mismatch and result ...

Страница 35: ...ect the best bit rate based on the current line conditions Manual Mode In Manual Mode the user can select one of the speed settings and the device will only attempt to attain the set speed If the line conditions degrade reducing the SNR or Signal to Noise Ratio but the de vice is able to maintain the link an alarm will be triggered to notify the user of the reduced SNR By configuring the Rescan Mo...

Страница 36: ...297 ft 25 0 9 km 2953 ft 20 1 0 km 3280 ft 15 1 3 km 4265 ft 10 1 7 km 5577 ft 5 2 0 km 6562 ft 2 5 2 5 km 8202 ft 1 2 Long Reach EoVDSL Performance Characteristics On No 24 AWG Polyethylene Insulated Cable PIC twisted pair wiring the following performance is typical with Long Reach EoVDSL Distance km Distance ft Downstream Mas ter to Slave Mbps Upstream Slave to Master Mbps 0 50 1600 40 20 1 00 3...

Страница 37: ...Communication Ports 4 3 3 EoVDSL Performance 28 RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 ...

Страница 38: ...100 VAC 240 VAC 3 15 A T 4 kVAC 10 W 24 12 VDC 24 VDC 3 15 A T 1 5 kVDC 10 W 48 37 VDC 72 VDC 3 15 A T 1 5 kVDC 10 W a T denotes time delay fuse b Power consumption varies based on configuration Non Hazardous Environments Input Voltage Power Sup ply Type Minimum Maximum Internal Fuse Rating a Isolation Maximum Power Con sumption b 88 VDC 300 VDC 3 15 A T 4 kVAC 10 W HI 85 VAC 264 VAC 3 15 A T 5 5 ...

Страница 39: ...Supported Networking Standards Standard 10 Mbps Ports 100 Mbps Ports 1000 Mbps Ports Description IEEE 802 1D ü ü ü MAC Bridges IEEE 802 1p ü ü ü Priority Levels IEEE 802 1Q ü ü ü VLAN Virtual LAN Tagging IEEE 802 3ab ü 1000Base Tx IEEE 802 3x ü ü ü Full Duplex Operation IEEE 802 3z ü 1000Base LX 5 4 Copper Ethernet Port Specifications The following details the specifications for copper Ethernet po...

Страница 40: ...es associate when determining maximum segment distances 10Base FL Fiber Optic Tx dBm Mode Connec tor Type Tx λ nm a Cable Type µm Mini mum Maxi mum Rx Sen sitivity dBm Rx Satu ration dBm Dis tance km a Power Budget dB 62 5 125 850 16 9 18 MM ST 50 125 850 19 8 12 8 34 11 2 2 14 2 a Typical 100Base FX Fiber Optic Tx dBm Mode Connec tor Type Tx λ nm a Cable Type μm Mini mum Maxi mum Rx Sen sitivity ...

Страница 41: ... Rate 300 to 230 kbps Connector DB9 or RJ45 Isolation 2 5 kV Fiber Serial Ports Mode Multimode Connector ST Typical Distance km 5 Optical Wavelength nm 850 Cable Size 50 125 or 62 5 125 5 7 Operating Environment The RUGGEDCOM RS910L is rated to operate under the following environmental con ditions Ambient Operating Tempera ture a 40 to 85 C 40 to 185 F Ambient Storage Temperature 40 to 85 C 40 to ...

Страница 42: ...ions Weight 1 2 kg 2 7 lbs Enclosure 20 AWG Galvanized Steel 5 9 Dimension Drawings Note All dimensions are in millimeters unless otherwise stated 99 06 187 96 168 66 65 3 116 59 7 87 Figure 5 1 Overall Dimensions RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 33 ...

Страница 43: ... Specifications 5 9 Dimension Drawings 13 64 101 6 11 2 78 74 120 65 194 06 83 20 183 90 128 4 Figure 5 2 Panel and DIN Rail Mount Dimensions 34 RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 ...

Страница 44: ...Safety Part 1 General Requirements CAN CSA C22 2 No 0 M91 General Requirements Canadian Electrical Code Part II CAN CSA C22 2 No 142 M1987 Process Control Equipment Industrial Products CAN CSA C22 2 No 213 16 Non Incendive Electrical Equipment for Use in Class I and II Division 2 and Class III Divisions 1 and 2 Hazardous Classified Locations Bi National Standard with ANSI ISA 12 12 01 2016 UL 916 ...

Страница 45: ...n expense IMPORTANT Changes or modifications not expressly approved by the party responsible for com pliance could void the user s authority to operate this device 6 1 3 FDA CDRH This device meets the requirements of the following U S Food and Drug Administra tion FDA standard Title 21 Code of Federal Regulations CFR Chapter I Sub chapter J Radiolog ical Health 6 1 4 ISED This device is declared b...

Страница 46: ...itional standards IEC 61000 6 2 Electromagnetic Compatibility EMC Part 6 2 Generic Standards Immunity for Industrial Environments 6 2 EMC and Environmental Type Tests The RUGGEDCOM RS910L has passed the following Electromagnetic Compatibility EMC and environmental tests EMC Type Tests Test Description Test Levels Severi ty Levels Enclosure Contact 8 kV 4 IEC 61000 4 2 ESD Enclosure Air 15 kV 4 IEC...

Страница 47: ... Ports 2 5 kV Common Mode 1 MHz 1 kV Differential Mode 1 MHz 3 IEC 61000 4 12 Damped Oscillatory AC Pow er Ports 2 5 kV Common Mode 1 MHz 1 kV Differential Mode 1 MHz 3 Signal Ports 30 V Continuous 300 V for 1 s 4 IEC 61000 4 16 Mains Frequency Voltage DC Pow er Ports 30 V Continuous 300 V for 1 s 4 IEC 61000 4 17 Ripple on DC Power Supply DC Pow er Ports 10 3 IEC 61000 4 29 Voltage Dips and Inter...

Страница 48: ...2 5 kV Common Mode 1 MHz DC Power Ports 2 5 kV Common and Dif ferential Mode 1 MHz Oscillatory AC Power Ports 2 5 kV Common and Dif ferential Mode 1 MHz Signal Ports 5 kV Failsafe Relay DC Power Ports 5 kV HV Impulse AC Power Ports 5 kV Signal Ports 2 kV Failsafe Relay DC Power Ports 2 kV Dielectric Strength AC Power Ports 2 kV Environmental Type Tests Test Description Test Levels Severity Levels ...

Страница 49: ...Certification 6 2 EMC and Environmental Type Tests 40 RUGGEDCOM RS910L Installation Manual 02 2020 C79000 G8976 1030 06 ...

Страница 50: ...ttps www siemens com ruggedcom Industry Online Support service and support https support industry siemens com Industry Mall https mall industry siemens com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY ...

Отзывы: