Chapter 6
Certification
RUGGEDCOM RS900GP
Installation Guide
34
Other Approvals
Section 6.1.8
Other Approvals
This device meets the requirements of the following additional standards:
•
EN50121-4
Railway applications – Electromagnetic Compatibility – Emission and Immunity of the Signaling and
Telecommunications Apparatus
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS900GP has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Tests
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
x
Signal Ports
3
DC Power Ports
± 1.5 kV
x
IEC 61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 2 kV
3
Signal Ports
± 500 V Line-to-Earth
± 500 V Line-to-Line
x
IEC 61000-4-5
Surge
DC Power Ports
± 500 V Line-to-Earth
± 500 V Line-to-Line
x
Signal Ports
10 V
3
DC Power Ports
10 V
3
IEC 61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
40 A/m Continuous
1000 A/m for 1 s
IEC 61000-4-29
Voltage Dips and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.01 s
100% for 0.01 s
Signal Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
3
IEC 61000-4-12
Damped Oscillatory
DC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
3
Содержание RUGGEDCOM RS900GP
Страница 4: ...RUGGEDCOM RS900GP Installation Guide iv ...
Страница 10: ...Preface RUGGEDCOM RS900GP Installation Guide x Customer Support ...
Страница 14: ...Chapter 1 Introduction RUGGEDCOM RS900GP Installation Guide 4 Decommissioning and Disposal ...
Страница 24: ...Chapter 2 Installing the Device RUGGEDCOM RS900GP Installation Guide 14 Connecting Power ...
Страница 40: ...Chapter 5 Technical Specifications RUGGEDCOM RS900GP Installation Guide 30 Dimension Drawings ...
Страница 46: ...Chapter 6 Certification RUGGEDCOM RS900GP Installation Guide 36 EMC and Environmental Type Tests ...