Technical Instructions 

RDF30U Room Temperature Controller with LCD 

Document Number 155-335 

for Four-Pipe Fan Coil Units 

September 27, 2007 

Page 2 

Siemens Industry, Inc.

 

 

 

Accessories 

ARG70 

Adapter plate for 4-inch × 4-inch or 2-inch × 4-inch conduit boxes 

141-570  

Lockable thermostat guard 

QAH11.1 

Changeover/remote temperature sensor 

 

Warning/Caution 
Notations 

WARNING: 

 

Personal injury or loss of life may occur if you do not perform 
a procedure as specified. 

 

CAUTION: 

 

Equipment damage may occur if you do not follow a 
procedure as specified. 

 

Operation 

The controller acquires the room temperature via its integrated sensor or optional 
external return air temperature sensor (QAH11.1) and maintains the setpoint by 
delivering two-position valve control output commands. 

The switching differential is 2 K (3.6

F) in Heating mode (adjustable in Parameter 10) 

and 1 K (1.8

F) in Cooling mode (adjustable in Parameter 11). 

Fan Operation 

The fan is switched to the selected speed via control output 12, 11 or 10. 

When 

the “Temperature-dependent fan control“ function is activated (can be selected 

with DIP Switch No. 1), the fan is switched on/off depending on the temperature, 
together with the valve. It is switched off when any of the following occurs: 

• 

leaving the heating or cooling sequence, provided the “Temperature-dependent fan 
co

ntrol“ function is activated. 

• 

manually changing to Standby   provided no setpoints (example, for freeze 
protection) are set and active. 

• 

activating an external operating mode changeover switch, provided application 
conditions do not call for Economy mode. 

• 

turning off the controller’s power supply. 

Display 

If DIP Switch No. 2 is set to ON (factory setting), the controller displays the measured 
room or return air temperature (unless parameters or setpoints are temporarily 
changed). If the DIP switch is set to OFF, the controller displays the Normal operating 
mode setpoint. In this case, the value of the current temperature reading can only be 
visualized temporarily by selecting Parameter P14. 

Water-based Fan Coil 
Application (Heating 
mode) 

When used in connection with four-pipe fan coils set DIP Switch No. 4 to ON

.

 

Use in conjunction with two valves, for heating and cooling operation. 

Heating Mode 

Terminals 4 and 2 (neutral) or 5 and 2 command the control valve. 

Output terminals 4 and 2 are closed (24 Vac) when: 

1.  the measured room temperature is half the switching differential below the setpoint 

(W, Heating mode), and 

2.  the valve has been closed for more than one minute (Parameter P20). 

Output terminals 4 and 2 are open (0 Vac) when: 

1.  the measured room temperature is half the switching differential above the setpoint 

(W, Heating mode), and 

Содержание RDF30U

Страница 1: ...ting mode changeover input for remote control Day Night Air movement control function for avoiding damage resulting from moisture Selectable installation and control parameters Display of room temperature or setpoint selectable Electronic minimum and maximum setpoint limits Operating voltage 24 Vac Application Typical use For controlling room temperature in individual rooms that are heated or cool...

Страница 2: ...wing occurs leaving the heating or cooling sequence provided the Temperature dependent fan control function is activated manually changing to Standby provided no setpoints example for freeze protection are set and active activating an external operating mode changeover switch provided application conditions do not call for Economy mode turning off the controller s power supply Display If DIP Switc...

Страница 3: ... the measured room temperature or the fan coil unit s return air temperature It detects if a QAH11 1 cable temperature sensor is connected to input 9 8 and then operates automatically according to that temperature Operating Modes Normal Mode Heating or Cooling mode with automatic changeover and manually selected fan speed III II or I In Normal mode the controller maintains the adjusted setpoint in...

Страница 4: ...g operation without opening the unit In the event of a power failure all set control parameters will be maintained Settings The parameters can be changed as follows 1 Set the operating mode selector to Standby 2 Press buttons and simultaneously for a minimum of three seconds Release them and within two seconds press the button again for three seconds The display will show P01 3 Select the required...

Страница 5: ... or switching differential heating NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 2 K 3 6 F P11 P band in Cooling mode or switching differential cooling NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 1 K 1 8 F P12 Dead zone in Normal mode 0 5 K to 10 K 1 F to 18 F in increments of 0 5 K 2 K 3 6 F ...

Страница 6: ...nical Design The controller consists of two parts Plastic housing which accommodates the electronics the operating elements and the built in room temperature sensor Base The housing engages in the base and is secured with two screws The base carries the screw terminals The DIP switches are located at the rear of the housing Setting and Operating Elements Figure 2 RDF30U Components 1 Display of the...

Страница 7: ... Changeover activated when switch is open 4 Output sequence Heating and cooling four pipe Two stage cooling Mounting Installation and Commissioning Notes Mounting location On a wall or inside the fan coil unit Do not mount in niches or bookshelves behind curtains above or near heat sources Do not mount in direct sunlight Mounting height is approximately 60 inches 1 5 m above the floor The connecti...

Страница 8: ...eter P09 Specifications Power Supply Operating voltage 24 Vac 20 25 Frequency 50 60 Hz Power consumption 6 VA maximum Fan control outputs 12 11 10 24 Vac Rating 5 3 A maximum Valve control output 4 6 NO 24 Vac 55 3 A maximum Return air temperature sensor QAH11 1 safety class II status input 9 8 NTC resistor 3 k at 77 F 25 C Status input D1 and GND Contact sensing SELV 6 to 15 Vdc 3 to 6 mA Insulat...

Страница 9: ...Terminals Figure 4 Wiring Terminals 1 2 24 Vac negative 3 24 Vac positive 4 Control valve output 24 Vac 5 Control valve output 24 Vac inverse of output 4 6 Control output second stage heating or cooling NO contact 8 Measuring neutral remote sensor 9 Return air temperature sensor 10 Control output Fan speed III 24 Vac 11 Control output Fan speed II 24 Vac 12 Control output Fan speed I 24 Vac D1 Sta...

Страница 10: ...rademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 335 Printed in the USA Page 10 Dimensions in Inches Millimeters Figure 6 R...