background image

RDF20U Room Temperature Controller with LCD 

Technical Instructions 

For Two-Pipe Fan Coil Units with Electric Heat 

Document Number 155-334 

 

September 27, 2007 

Siemens Industry, Inc. 

Page 7

 

 

Table 1.  Control Parameters. 

 

Para-

meter 

Description 

Setting Range 

Factory  

Setting 

P01 

Heating setpoint in Economy mode  
(operating mode changeover contact activated ) 

OFF,  
41

F to 68

F (5

C to 20

C) (in increments of 0.5 K) 

61

(16

C) 

P02 

Cooling setpoint in Economy mode  
(operating mode changeover contact activated ) 

OFF,  
70

F to 95

F (21

C to 35

C) (in increments of 0.5 K) 

82

(28

C) 

P03 

Heating setpoint in Standby 

 

OFF,  
41

F to 68

F (5

C to 20

C) (in increments of 0.5 K) 

46

F (8

C) 

P04 

Cooling setpoint in Standby 

 

OFF, 
70

F to 95

F (21

C to 35

C) (in increments of 0.5 K) 

OFF 

P05 

Minimum setpoint limit stops in Normal mode 

41

F to 68

F (5

C to 20

C) (in increments of 0.5 K) 

41

F (5°C) 

P06 

Maximum setpoint limit stops in Normal mode 

70

F to 95

F (21

C to 35

C) (in increments of 0.5 K) 

95

(35°C) 

P07 

Heating/cooling changeover cooling switching 
point  

50

F to 77

F (10

°C

 to 25

°

C) (in increments of 0.5 K) 

61

(16

C) 

P08 

Heating/cooling changeover heating switching 
point  

8

°

F to 104

°

F (27

°

C to 40

°

 C

)

 (in increments of 

0.5 K) 

82

(28

C) 

P09 

Sensor calibration 

-3K to 3 K (-5.4

°

F to 5.4

°

F) (in increments of 0.5 K) 

0 K (0

F) 

P10 

P-band in Heating mode or switching differential 
heating. 

NOTE:

 This parameter is in degrees 

Kelvin, 1 K = 1.8

F. 

0.5 K to 4 K (1

°

F to 7

°

F) (in increments of 0.5 K) 

2 K 
(3.6

°F)

 

P11 

P-band in Cooling mode or switching differential 
cooling. 

NOTE:

 This parameter is in degrees 

Kelvin, 1 K = 1.8

F. 

0.5 K to 4 K (1

°

F to 7

°

F) (in increments of 0.5 K) 

1 K 
(1.8

°F)

 

P12 

Dead zone in Normal mode 

0.5 K to 10 K (1

°

F to 18

°

F) (in increments of 0.5 K) 

2 K 
(3.6

°F)

 

P13 

Active temperature sensor (no setting, display 
only) 

1: Room temperature sensor active 

2: Return air temperature sensor active 

-- 

P14 

Value of current room temperature reading  
(no setting, display only) 

32

°

F to 120

°

F (0

°

C to 49

°

C) = current temperature 

value 

-- 

P15 

Value of current heating/cooling changeover 
temperature reading including indication of 

current mode (

, ) (no setting, display only)

 

100 = input open (no sensor connected, heating 

mode (

)

 

32

°

F to 120

°

F (0

°

C to 49

°

C) = current temperature 

value 
00 = input bridged, Cooling mode (

)

 

-- 

P16 

Purging function 

0 min.: Not active 
1 to 5 min.: Active with selected duration 

0 min. 

P17 

Fan control in Economy mode 
OFF: Fan is off in the dead zone 
ON: Fan is on in the dead zone, 

ON:  Running at the selected speed or at speed 1 if 
in Standby 

 

 

OFF 

P18 

Setpoint differential 

0.5 K to 5 K (1

°

F to 9

°

F) 

2 K 
(3.6

°F)

 

P19 

Minimum output on time (4, 6) 

1 to 20 minutes (in increments of 1 min.) 

1 min.

 

 

P20 

Minimum output off time (4, 6) 

1 to 20 minutes (in increments of 1 min.) 

1 min.

 

 

P21 

Fan overrun 

0 to 300 seconds (in increments of 10 seconds) 

60 s 

P22 

Point of reference for setpoint in Normal mode 

HA: Heating sequence; CL: Cooling sequence 

HA 

P23 

Display unit of measure 

°

F, 

°

°

Содержание RDF20U

Страница 1: ... and Standby Operating mode changeover input for remote control Day Night Air movement control function for avoiding damage resulting from moisture Selectable installation and control parameters Display of room temperature or setpoint selectable Electronic minimum and maximum setpoint limits Operating voltage 24 Vac Application Typical use Control of the room temperature in individual rooms that a...

Страница 2: ...an is switched on off depending on the temperature together with the valve It is switched off when any of the following occurs leaving the heating or cooling sequence provided the Temperature dependent fan control function is activated manually changing to Standby provided no setpoints example for freeze protection are set and active activating an external operating mode changeover switch provided...

Страница 3: ...sured room temperature is half the switching differential above the Cooling Mode setpoint W and 2 the valve has been open for more than one minute Parameter 19 NOTE Terminal output 5 NC delivers a control command which is inverted to the control command at output 4 NO and can be used for Normally Open valves Automatic Changeover The water temperature measured by the changeover sensor QAH11 1 is us...

Страница 4: ...16 and exiting the parameter setting mode Return Air Temperature Optional The RDF20U provides control based on the measured room temperature or the fan coil unit s return air temperature It detects if a QAH11 1 cable temperature sensor is connected to input 8 9 and then operates automatically according to that temperature Electric Heat Active in Heating Mode NOTE This function is not active when u...

Страница 5: ...eating Mode Hot Water Plus Electric Heat Figure 5 Cooling Mode with Optional Electric Heat DIP Switch 4 ON Electric Heat Enabled Figure 6 Cooling Mode Chilled Water DIP Switch 4 OFF Electric Heat Disabled T F Room temperature w Room temperature setpoint wD Setpoint differential Y Heating cooling valve output voltage E Electric heat SDH Switching differential Heating SDC Switching differential Cool...

Страница 6: ...ous fan To avoid damage due to moisture in very warm and humid climates resulting from lack of air circulation in Economy mode for example in hotel rooms during unoccupied periods the fan can be kept running in Economy mode when activating Parameter P17 In this case the fan keeps running at the selected speed or at speed I if the operating mode selector is in Standby Setting the Control Parameters...

Страница 7: ... This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 2 K 3 6 F P11 P band in Cooling mode or switching differential cooling NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 1 K 1 8 F P12 Dead zone in Normal mode 0 5 K to 10 K 1 F to 18 F in increments of 0 5 K 2 K 3 6 F P13 Active temperature sensor no settin...

Страница 8: ...155 321P25 Mechanical Design The controller consists of two parts Plastic housing which accommodates the electronics the operating elements and the built in room temperature sensor Base The housing engages in the base and is secured with two screws The base carries the screw terminals The DIP switches are located at the rear of the housing Setting and Operating Elements Figure 7 RDF20U Components ...

Страница 9: ...erature sensor can be replaced by an external switch suited for live voltage for manual changeover In systems with continuous heating mode no sensor is connected to the controller s input In systems with continuous cooling mode the controller input 7 8 must be bridged Mounting Installation and Commissioning Notes Mounting location On a wall or inside the fan coil unit Do not mount in niches or boo...

Страница 10: ...put 4 2 NO 24 Vac Rating 5 3 A maximum Valve control output 5 2 NC 24 Vac Rating 5 3 A maximum Electric heat control output 6 2 NO 24 Vac Rating 5 3 A maximum Return air temperature sensor QAH11 1 safety class II status input 9 8 NTC resistor 3K at 77 F 25 C Changeover status input 7 8 QAH11 1 safety class II NTC resistor 3K at 77 F 25 C Status input D1 and GND Contact sensing SELV 6 to 15 Vdc 3 t...

Страница 11: ...minals Figure 9 Wiring Terminals 1 2 24 Vac negative 3 24 Vac positive 9 Return air temperature sensor 8 Measuring neutral 7 Changeover sensor D1 GND Potential free operating mode changeover switch operating action can be selected 12 Control output Fan speed I 24 Vac 11 Control output Fan speed II 24 Vac 10 Control output Fan speed III 24 Vac 4 Control output Valve 24 Vac 5 Control output Valve 24...

Страница 12: ...ademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 334 Printed in the USA Page 12 Dimensions In Inches Millimeters Figure 11 R...

Отзывы: