RDF20U Room Temperature Controller with LCD 

Technical Instructions 

For Two-Pipe Fan Coil Units with Electric Heat 

Document Number 155-334 

 

September 27, 2007 

Siemens Industry, Inc. 

Page 9

 

 

Table 3.  DIP Switches. 

DIP Switch 

No. 

Description 

Position ON (Factory Setting) 

Position OFF 

Fan control 

Fan control is temperature-
independent 

Fan control is temperature-
dependent 

Display of temperature or setpoint 

Room (or return air) temperature 
display 

Setpoint display 

 

Operating action of switch for external 
operating mode changeover 

Changeover activated when switch is 
closed (NO) 

Changeover activated when 
switch is open (NC) 

Electric heat 

Active in Cooling mode 

Inactive in Cooling mode 

 

 

Engineering Notes 

With the RDF20U, the controller input for automatic heating/cooling changeover can 
also be used without the QAH11.1 cable temperature sensor: 

 

In systems without automatic changeover, the temperature sensor can be replaced 
by an external switch (suited for live voltage) for manual changeover. 

 

In systems with continuous heating mode, no sensor is connected to the 
controller’s input. 

 

In systems with continuous cooling mode, the controller input (7-8) must be 
bridged. 

Mounting, 
Installation and 
Commissioning 
Notes 

 

Mounting location: On a wall or inside the fan coil unit.  

 

Do not mount in niches or bookshelves, behind curtains, above or near heat 
sources.  

 

Do not mount in direct sunlight.  

 

Mounting height is approximately 60 inches (1.5 m) above the floor.  

 

The connecting wires can be run to the controller from a recessed conduit box. 

 

Figure 8.  Acceptable Mounting Height in Inches. 

 

Check the positions of the DIP switches and change them, if required.  

 

After applying power, the controller makes a reset during which all LCD segments 
flash, indicating that the reset has been correctly made. This takes about three 
seconds. Then, the controller is ready to operate. 

 

Prior to installing the changeover sensor, thermal conductive paste must be applied 
to the location on the pipe where the sensor is placed. 



Содержание RDF20U

Страница 1: ... and Standby Operating mode changeover input for remote control Day Night Air movement control function for avoiding damage resulting from moisture Selectable installation and control parameters Display of room temperature or setpoint selectable Electronic minimum and maximum setpoint limits Operating voltage 24 Vac Application Typical use Control of the room temperature in individual rooms that a...

Страница 2: ...an is switched on off depending on the temperature together with the valve It is switched off when any of the following occurs leaving the heating or cooling sequence provided the Temperature dependent fan control function is activated manually changing to Standby provided no setpoints example for freeze protection are set and active activating an external operating mode changeover switch provided...

Страница 3: ...sured room temperature is half the switching differential above the Cooling Mode setpoint W and 2 the valve has been open for more than one minute Parameter 19 NOTE Terminal output 5 NC delivers a control command which is inverted to the control command at output 4 NO and can be used for Normally Open valves Automatic Changeover The water temperature measured by the changeover sensor QAH11 1 is us...

Страница 4: ...16 and exiting the parameter setting mode Return Air Temperature Optional The RDF20U provides control based on the measured room temperature or the fan coil unit s return air temperature It detects if a QAH11 1 cable temperature sensor is connected to input 8 9 and then operates automatically according to that temperature Electric Heat Active in Heating Mode NOTE This function is not active when u...

Страница 5: ...eating Mode Hot Water Plus Electric Heat Figure 5 Cooling Mode with Optional Electric Heat DIP Switch 4 ON Electric Heat Enabled Figure 6 Cooling Mode Chilled Water DIP Switch 4 OFF Electric Heat Disabled T F Room temperature w Room temperature setpoint wD Setpoint differential Y Heating cooling valve output voltage E Electric heat SDH Switching differential Heating SDC Switching differential Cool...

Страница 6: ...ous fan To avoid damage due to moisture in very warm and humid climates resulting from lack of air circulation in Economy mode for example in hotel rooms during unoccupied periods the fan can be kept running in Economy mode when activating Parameter P17 In this case the fan keeps running at the selected speed or at speed I if the operating mode selector is in Standby Setting the Control Parameters...

Страница 7: ... This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 2 K 3 6 F P11 P band in Cooling mode or switching differential cooling NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 1 K 1 8 F P12 Dead zone in Normal mode 0 5 K to 10 K 1 F to 18 F in increments of 0 5 K 2 K 3 6 F P13 Active temperature sensor no settin...

Страница 8: ...155 321P25 Mechanical Design The controller consists of two parts Plastic housing which accommodates the electronics the operating elements and the built in room temperature sensor Base The housing engages in the base and is secured with two screws The base carries the screw terminals The DIP switches are located at the rear of the housing Setting and Operating Elements Figure 7 RDF20U Components ...

Страница 9: ...erature sensor can be replaced by an external switch suited for live voltage for manual changeover In systems with continuous heating mode no sensor is connected to the controller s input In systems with continuous cooling mode the controller input 7 8 must be bridged Mounting Installation and Commissioning Notes Mounting location On a wall or inside the fan coil unit Do not mount in niches or boo...

Страница 10: ...put 4 2 NO 24 Vac Rating 5 3 A maximum Valve control output 5 2 NC 24 Vac Rating 5 3 A maximum Electric heat control output 6 2 NO 24 Vac Rating 5 3 A maximum Return air temperature sensor QAH11 1 safety class II status input 9 8 NTC resistor 3K at 77 F 25 C Changeover status input 7 8 QAH11 1 safety class II NTC resistor 3K at 77 F 25 C Status input D1 and GND Contact sensing SELV 6 to 15 Vdc 3 t...

Страница 11: ...minals Figure 9 Wiring Terminals 1 2 24 Vac negative 3 24 Vac positive 9 Return air temperature sensor 8 Measuring neutral 7 Changeover sensor D1 GND Potential free operating mode changeover switch operating action can be selected 12 Control output Fan speed I 24 Vac 11 Control output Fan speed II 24 Vac 10 Control output Fan speed III 24 Vac 4 Control output Valve 24 Vac 5 Control output Valve 24...

Страница 12: ...ademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 334 Printed in the USA Page 12 Dimensions In Inches Millimeters Figure 11 R...

Отзывы: