Technical Instructions 

RDF20U Room Temperature Controller with LCD 

Document Number 155-334 

for Two-Pipe Fan Coil Units with Electric Heat 

September 27, 2007 

Page 4 

Siemens Industry, Inc.

 

 

 
Automatic Changeover, 
Continued 

In systems without automatic changeover, the temperature sensor can be replaced by 
an external switch (D1, GND) (must be suited for live voltage) for manual changeover. 
In systems with continuous heating mode, no sensor will be connected to the 
controller’s input. With continuous cooling mode, the controller (7/8) input must be 
bridged. 

Purging Function 
(Optional) 

The changeover sensor initiates the change from Heating to Cooling mode, based on 
the measured water temperature. If a two-way valve is used, it is highly recommended 
to activate the purging function (adjustable in Parameter P16). This function ensures 
the correct acquisition of the medium temperature even if the two-way valve is closed 
for a longer period of time. To achieve this, the valve is opened for one to five minutes 
(adjustable in Parameter P16) at two-hour intervals during off hours. 

When the purging function is activated, the first purging action is performed after 
changing Parameter P16 and exiting the parameter setting mode.

  

Return Air Temperature 
(Optional) 

The RDF20U provides control based on the measured room temperature or the fan coil 
unit’s return air temperature. It detects if a QAH11.1 cable temperature sensor is 
connected to input 8-9 and then operates automatically according to that temperature. 

Electric Heat, Active in 
Heating Mode 

NOTE: 

This function is not active when using thermal actuators. 

In addition to hot water heating, the electric heat receives an ON command via output 6 
when: 

 

the measured room temperature is x 

 w 

 w

D

 

 1/2 SDH, and 

 

the electric heat has been switched off for more than one minute. 

The OFF command for the electric heat is given when: 

1.  the measured room temperature is x 

 w 

 w

D

 

+

 1/2 SDH, and  

2.  the electric heat has been switched on for more than one minute. 

Electric Heat, Active in 
Cooling Mode 

For this operation, DIP Switch No. 4 must be set to ON (factory setting).  
The electric heat receives the ON command via control output 6 when: 

1.  the measured room temperature is half the switching differential below the adjusted 

setpoint, and 

2.  the electric heat has been switched off for more than one minute. 

The OFF command for the electric heat is given when: 

1.  the measured room temperature is half the switching differential above the adjusted 

setpoint, and 

2.  the electric heat has been switched on for more than one minute. 

Содержание RDF20U

Страница 1: ... and Standby Operating mode changeover input for remote control Day Night Air movement control function for avoiding damage resulting from moisture Selectable installation and control parameters Display of room temperature or setpoint selectable Electronic minimum and maximum setpoint limits Operating voltage 24 Vac Application Typical use Control of the room temperature in individual rooms that a...

Страница 2: ...an is switched on off depending on the temperature together with the valve It is switched off when any of the following occurs leaving the heating or cooling sequence provided the Temperature dependent fan control function is activated manually changing to Standby provided no setpoints example for freeze protection are set and active activating an external operating mode changeover switch provided...

Страница 3: ...sured room temperature is half the switching differential above the Cooling Mode setpoint W and 2 the valve has been open for more than one minute Parameter 19 NOTE Terminal output 5 NC delivers a control command which is inverted to the control command at output 4 NO and can be used for Normally Open valves Automatic Changeover The water temperature measured by the changeover sensor QAH11 1 is us...

Страница 4: ...16 and exiting the parameter setting mode Return Air Temperature Optional The RDF20U provides control based on the measured room temperature or the fan coil unit s return air temperature It detects if a QAH11 1 cable temperature sensor is connected to input 8 9 and then operates automatically according to that temperature Electric Heat Active in Heating Mode NOTE This function is not active when u...

Страница 5: ...eating Mode Hot Water Plus Electric Heat Figure 5 Cooling Mode with Optional Electric Heat DIP Switch 4 ON Electric Heat Enabled Figure 6 Cooling Mode Chilled Water DIP Switch 4 OFF Electric Heat Disabled T F Room temperature w Room temperature setpoint wD Setpoint differential Y Heating cooling valve output voltage E Electric heat SDH Switching differential Heating SDC Switching differential Cool...

Страница 6: ...ous fan To avoid damage due to moisture in very warm and humid climates resulting from lack of air circulation in Economy mode for example in hotel rooms during unoccupied periods the fan can be kept running in Economy mode when activating Parameter P17 In this case the fan keeps running at the selected speed or at speed I if the operating mode selector is in Standby Setting the Control Parameters...

Страница 7: ... This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 2 K 3 6 F P11 P band in Cooling mode or switching differential cooling NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 1 K 1 8 F P12 Dead zone in Normal mode 0 5 K to 10 K 1 F to 18 F in increments of 0 5 K 2 K 3 6 F P13 Active temperature sensor no settin...

Страница 8: ...155 321P25 Mechanical Design The controller consists of two parts Plastic housing which accommodates the electronics the operating elements and the built in room temperature sensor Base The housing engages in the base and is secured with two screws The base carries the screw terminals The DIP switches are located at the rear of the housing Setting and Operating Elements Figure 7 RDF20U Components ...

Страница 9: ...erature sensor can be replaced by an external switch suited for live voltage for manual changeover In systems with continuous heating mode no sensor is connected to the controller s input In systems with continuous cooling mode the controller input 7 8 must be bridged Mounting Installation and Commissioning Notes Mounting location On a wall or inside the fan coil unit Do not mount in niches or boo...

Страница 10: ...put 4 2 NO 24 Vac Rating 5 3 A maximum Valve control output 5 2 NC 24 Vac Rating 5 3 A maximum Electric heat control output 6 2 NO 24 Vac Rating 5 3 A maximum Return air temperature sensor QAH11 1 safety class II status input 9 8 NTC resistor 3K at 77 F 25 C Changeover status input 7 8 QAH11 1 safety class II NTC resistor 3K at 77 F 25 C Status input D1 and GND Contact sensing SELV 6 to 15 Vdc 3 t...

Страница 11: ...minals Figure 9 Wiring Terminals 1 2 24 Vac negative 3 24 Vac positive 9 Return air temperature sensor 8 Measuring neutral 7 Changeover sensor D1 GND Potential free operating mode changeover switch operating action can be selected 12 Control output Fan speed I 24 Vac 11 Control output Fan speed II 24 Vac 10 Control output Fan speed III 24 Vac 4 Control output Valve 24 Vac 5 Control output Valve 24...

Страница 12: ...ademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 334 Printed in the USA Page 12 Dimensions In Inches Millimeters Figure 11 R...

Отзывы: