9
INSTALLATION
Remove all system power before
installation, first battery and then AC.
(To power up, connect the
AC first, then the battery.)
The RCM-1 has two configuration dipswitches,
S1 and S2.
Set the dipswitches before install-
ing the RCM-1 into the OMM-1/2.
(See NOTE
following Table 4 for the operation of
dipswitches.)
The RCM-1 takes up one of the 255 possible
network addresses. Use switch S1 to set the
MXL network address. Set this switch according
to the address where the RCM-1 is installed in
the MXL’s network map. Refer to the AccuLINK
(CSG-M) configuration printout for the address of
the module. See Table 3 for settings.
In addition to S1 which is used to set the network
address, the RCM-1 has a second bank of
dipswitches, S2, which must be correctly config-
ured for the RCM-1 to operate properly. Refer to
Table 4 for a description of the functions for each
of the switches in S2.
Application 8
Combination Wire and Fiber Installation
Application 9
Style 4 Repeater Installation