background image

18

Combination Fiber and Wire Style 4
Connection - Application 8 (See Figure 10)

The RCM-1 can support a combination of fiber
optics and wire which can be used to connect
to other systems which require global paging
capability.

Figure 10

Combination Fiber and Wire Connection

To fiber optic module from Fiber Optic Model D2300CP.

Port B receive from transmit out on other RCMs.

No connection if first RCM.

Port B transmit pair to receive inputs on other RCMs.

No connection if last RCM.

To OCC-1, TB 2/TB4, 1

To OCC-1, TB 2/TB4, 2

To TBM-2, TB5, 1

To TBM-2, TB5, 4

+

+

_

_

1
2
3
4
5
6
7
8
9

10

11

12
13
14
15
16
17
18
19
20
21
22

1
2
3
4
5
6
7
8
9

10

11

12
13
14
15
16
17
18
19
20
21
22

NOT USED

CABLE TO
MMB OR PSR
P/N 555-190967

RCM-1

OMM-1

or

OMM-2

NOT USED

NOT USED

Notes:

1. Use 18AWG minimum wire.

2. Limit the maximum resistance of loop total from the first RCM to

the last RCM to 100 ohms. Maximum line capacitance = 1µF.

3. The wiring is power limited to NFPA 70 per NEC 760.

4. Maximum voltage is 1.5V RMS.

5. Maximum current is 50mA.

6. Refer to Figure 12 for proper EOLR placement.

7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV

Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.

8. Positive and negative ground fault detected at <50K ohms for

terminals 1-6 and 17-20.

S

G

N

I

T

T

E

S

2

S

W

S

n

o

i

t

p

i

r

c

s

e

D

n

o

i

t

a

c

o

L

B

n

o

i

t

a

c

o

L

C

n

o

i

t

a

c

o

L

D

1

g

i

f

n

o

c

r

e

p

p

o

C

f

f

o

n

o

f

f

o

2

g

i

f

n

o

c

r

e

p

p

o

C

n

o

f

f

o

f

f

o

3

g

i

f

n

o

c

r

e

p

p

o

C

n

o

n

o

n

o

4

r

e

t

a

e

p

e

r

r

e

p

p

o

C

n

o

n

o

n

o

5

g

i

f

n

o

c

r

e

b

i

F

f

f

o

n

o

n

o

6

g

i

f

n

o

c

r

e

b

i

F

n

o

n

o

n

o

7

7

e

l

y

t

S

n

o

n

o

n

o

Содержание RCM-1

Страница 1: ...lation Instructions Model RCM 1 Riser Control Module Fire Safety Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN ...

Страница 2: ... C Fiber Optic Extension 8 Application 8 Combination Wire and Fiber Installation 9 Application 9 Style 4 Repeater Installation 9 INSTALLATION 9 Network Address Programming S1 Table 3 10 S2 Settings Table 4 11 Application 1 Typical Style 4 Connections 12 Application 2 Typical Style 4 Connections with PORT C Extension 13 Application 3 Typical Style 7 Connections 14 Application 4 Style 7 Connections ...

Страница 3: ...fer to Figure 2 for their location PORT STYLE FUNCTION A 6 Audio signal input B 4 7 Audio signal input output C 4 Audio signal output D 6 Audio signal output The RCM 1 supervises Port B for open and short circuits reports by exception to the MXL and isolates the fault INTRODUCTION The Model RCM 1 Riser Control module from Siemens Building Technologies Inc provides control and supervision of global...

Страница 4: ...en Lights when the RCM 1 transmits voice using the copper wire XMIT connections XMIT F Green Lights when the RCM 1 transmits voice using any of the fiber optic ports LM1 Green Lights when the RCM 1 is in local mode Flashes when there is no valid carrier on the riser GM1 Green Lights when the RCM 1 is in global mode 1 Flashes when there is no valid carrier on the riser GM2 Green Lights when the RCM...

Страница 5: ...ptic transmission 6 Style 4 fiber optic with a Style 4 fiber optic output only extension 7 Style 7 fiber connections with a Style 4 output only fiber extension 8 Combination wire and fiber installation 9 Style 4 Repeater Installation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 PORT C Copper Interface Transmit Style 4 CT4 PORT B ...

Страница 6: ...ical Style 4 Installation Application 3 Typical Style 7 Installation Application 2 Style 4 with a Style 4 Output Only Extension RCM 1 Nos 4 5 and 6 have local ACMs but cannot output to the global bus they can only receive ...

Страница 7: ...7 Application 4 Style 7 with a PORT C Extension Application 5 Style 4 Fiber Optic Installation ...

Страница 8: ...8 Application 6 Style 4 Fiber Optic with a PORT C Fiber Optic Extension Application 7 Style 7 Fiber Optic with a PORT C Fiber Optic Extension ...

Страница 9: ...1 to set the MXL network address Set this switch according to the address where the RCM 1 is installed in the MXL s network map Refer to the AccuLINK CSG M configuration printout for the address of the module See Table 3 for settings In addition to S1 which is used to set the network address the RCM 1 has a second bank of dipswitches S2 which must be correctly config ured for the RCM 1 to operate ...

Страница 10: ...O X X X O X X X O X X X O O O O X X X X O X O O X X X X O O X O X X X X O X X O X X X X O O O X X X X X O X O X X X X X O O X X X X X X O X X X X X X X O 8 2 1 9 2 1 0 3 1 1 3 1 2 3 1 3 3 1 4 3 1 5 3 1 6 3 1 7 3 1 8 3 1 9 3 1 0 4 1 1 4 1 2 4 1 3 4 1 4 4 1 5 4 1 6 4 1 7 4 1 8 4 1 9 4 1 0 5 1 1 5 1 2 5 1 3 5 1 4 5 1 5 5 1 6 5 1 7 5 1 8 5 1 9 5 1 0 6 1 1 6 1 2 6 1 3 6 1 4 6 1 5 6 1 6 6 1 7 6 1 8 6 1 ...

Страница 11: ...nection 1 0 Spare 0 0 Spare 7 Style On for Style 4 Off for Style 7 NOTE To open a dipswitch press down on the side of the dipswitch marked OPEN To close a dipswitch press down on the side of the dipswitch opposite the side marked OPEN To open a slide switch push the slide to the side opposite the side marked ON To close a slide switch push the slide to the side marked ON Use switch S2 to set the c...

Страница 12: ...UTION INSERT THE RCM 1 MODULE IN THE OMM 1 2 WITH THE ELECTRONIC COMPONENTS FACING OUTWARD TOWARDSTHEOMMSCREWTERMINALS INSTALLATION IN ANY OTHER WAY WILL CAUSE DAMAGE TO THE RCM 1 Typical Style 4 Connections Application 1 See Figure 4 This is the basic configuration of the RCM 1 It allows multiple networked MXL voice systems to be connected together to act as one large integrated voice evacuation ...

Страница 13: ... supported Notes 1 Use 18AWG minimum wire 2 Limit the maximum resistance of loop total from the first RCM to the last RCM to 100 ohms Maximum line capacitance 1µF 3 The wiring is power limited to NFPA 70 per NEC 760 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figure 12 for proper EOLR placement 7 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 re...

Страница 14: ... line capacitance 1µF 3 The wiring is power limited to NFPA 70 per NEC 760 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figure 12 for proper EOLR placement 7 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information 8 Positive and negative ground fault detected at 50K ohms for terminals 17 20 Typical St...

Страница 15: ... 13 14 15 16 17 18 19 20 21 22 NOT USED CABLE TO MMB OR PSR P N 555 190967 RCM 1 OMM 1 or OMM 2 NOT USED NOT USED NOT USED Notes 1 Use 18AWG minimum wire 2 Limit the maximum resistance of loop total from the first RCM to the last RCM to 100 ohms Maximum line capacitance 1µF 3 The wiring is power limited to NFPA 70 per NEC 760 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figur...

Страница 16: ...60 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figure 12 for proper EOLR placement 7 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information 8 Positive and negative ground fault detected at 50K ohms for terminals 1 6 and 17 20 Typical Style 4 Fiber Optic Connections with Optional PORT C Extension App...

Страница 17: ...PA 70 per NEC 760 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figure 12 for proper EOLR placement 7 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information 8 Positive and negative ground fault detected at 50K ohms for terminals 1 6 and 17 20 Typical Style 7 Fiber Optic Connections with Optional PORT ...

Страница 18: ...1 or OMM 2 NOT USED NOT USED Notes 1 Use 18AWG minimum wire 2 Limit the maximum resistance of loop total from the first RCM to the last RCM to 100 ohms Maximum line capacitance 1µF 3 The wiring is power limited to NFPA 70 per NEC 760 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figure 12 for proper EOLR placement 7 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems...

Страница 19: ...m wire 2 Limit the maximum resistance of loop total from the first RCM to the last RCM to 100 ohms Maximum line capacitance 1µF 3 The wiring is power limited to NFPA 70 per NEC 760 4 Maximum voltage is 1 5V RMS 5 Maximum current is 50mA 6 Refer to Figure 12 for proper EOLR placement 7 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional w...

Страница 20: ...Style 4 connections to the OCC Figure 12 Wiring Configurations for the OCC and ACM P N 315 093878 11 RCM Style 6 connections to the OCC RCM Style 4 connections to the ACM RCM Style 6 connections to the ACM ...

Отзывы: