background image

5 / 6

Siemens

Flow switch QVE1902.0..

CM1N1596en

Building Technologies

2017-02-16

Disposal

The device is considered an electronics device for disposal in terms of European

Directive 2012/19/EU and may not be disposed of as domestic garbage.

x

  Dispose of the device through channels provided for this purpose.

x

  Comply with all local and currently applicable laws and regulations.

Technical data

Field of use

Permissible media

Medium temperature

Piping diameter

Nominal pressure

All liquids

(not suitable for ammonia)

-20…100 °C (Medium may not freeze)

DN 10…25

PN 10

(piping approved for PN 25)

Contact

Type of switch

Max. contact rating

Max. switching capacity

Length of connecting cable/cross section

External supply line protection (EU)

Closes as flow increases

*)

Opens as flow decreases

*)

Reed contact

AC 230 V, 1 A / DC 48 V, 1 A

26 VA or 20 W

1.5 m / 0.5 mm

2

Fuse slow max. 10 A

or

Circuit breaker max. 13 A

Characteristic B, C, D according to

or

Power source with current limitation of

max. 10 A

Switching point adjustment

Setting range

Manual, set at the factory to the middle of

the setting range

See Sizing on page 2

Protection class

Housing

II according to EN 60730-1

IP65 according to EN 60529

Storage, transportation, operation

 Temperature

 Humidity

0…70 °C

<95 % r.h.

Product standard

EN 60204-1

Safety of machinery - Electrical

equipment of machines

EU Conformity (CE)

CM1T1596xx

**)

The product environmental declaration CE1E1596

**)

 contains data on

environmentally compatible product design and assessments (RoHS compliance,

materials composition, packaging, environmental benefit, disposal).
Excl. packaging

See under "Dimensions and weight"

Switching unit/connecting cable

Housing and paddle system/piping

Polyamide / PVC

PPE+PS Noryl FE1630PW / brass
Black

*) Applies to delivery state (switching function can be inverted as needed).
**) The documents can be downloaded from

http://siemens.com/bt/download

.

Functional data

general

Switching function

Degree of protection

Environmental conditions

Standards and Directives

Environmental

compatibility

Dimensions / Weight

Material

Housing color

Hindustan Hydraulics & Pneumatics,  Chennai - 01. 

Phone : 2534 3066, 2534 5625, 2534 5587
E-Mail : [email protected]

Contact person : V. Anandha krishnan - 98409 21885

Содержание QVE1902.010

Страница 1: ...act setting NO NC contact x Housing protection type IP 65 Protection class II x Maintenance free Use In HVAC plants to monitor the flow of liquid medium in hydraulic systems in particular refrigeration heat pump and heating plants e g for evaporators boilers heat exchangers etc Hindustan Hydraulics Pneumatics Chennai 01 Phone 2534 3066 2534 5625 2534 5587 E Mail hhp hindustanhydraulic in Contact p...

Страница 2: ...nder no circumstances may the indicated limit values see Technical data be exceeded x You must ensure that the materials used in the flow switch are sufficiently chemically and mechanically durable against the medium to be monitored as well as external influences x Comply with maximum contact load for the reed contact The maximum contact load indicated on the type label applies to Ohm loads only a...

Страница 3: ...ng that the arrow points parallel to the pipe axis and indicates the direction of flow x Install the section of piping for the flow switch the same as a valve in the existing piping Installation notes x Comply with all local regulations on electrical systems x Only qualified personnel may do the electrical installation x Always de energize the system before connecting the wires of the mains cable ...

Страница 4: ...int Adjust to the arrowhead means Switching point is at a lower flow rate Adjust to the arrow end Switching point is at a higher flow rate x Carefully retighten the locking screw x We recommend using thread locker to secure the locking screw on the switching unit after carrying out individual adjustments NO contact red arrow NC white arrow Operating notes x Please make sure that there are no exter...

Страница 5: ...ent Setting range Manual set at the factory to the middle of the setting range See Sizing on page 2 Protection class Housing II according to EN 60730 1 IP65 according to EN 60529 Storage transportation operation Temperature Humidity 0 70 C 95 r h Product standard EN 60204 1 Safety of machinery Electrical equipment of machines EU Conformity CE CM1T1596xx The product environmental declaration CE1E15...

Страница 6: ...15 46 0 105 5 239 QVE1902 025 DN 25 130 G1 15 55 5 115 5 315 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2017 Delivery and technical specifications subject to change Hindustan Hydraulics Pneumatics Chennai 01 Phone 2534 3066 2534 5...