Flow switch QVE1902.0..

CM1N1596en

Building Technologies

2017-02-16

Type summary

Type / ASN

Order number (SSN)

Name

QVE1902.010

S55720-S199

Flow switch

QVE1902.015

S55720-S200

Flow switch

QVE1902.020

S55720-S201

Flow switch

QVE1902.025

S55720-S202

Flow switch

Ordering

When ordering, please specify the quantity, type, and product name.

Sizing

Switching value table for water at 20 °C

Type

 (ASN)

DN

Threading

[inch]

Q

max

[l/min]

Factory setting

(range) [l/min]

QVE1902.010 DN 10

20

3.2 (2.8…3.7)

2.7 (2.0…3.4

3.6 (3.1…4.1)

QVE1902.015 DN 15

½

30

4.2 (3.6…4.9)

3.4 (2.8…4.0)

4.4 (3.7…5.1)

QVE1902.020 DN 20

¾

80

7.6 (6.9…8.4)

7.1 (6.1…8.2)

8.7 (8.0…9.5)

QVE1902.025 DN 25

1

130  12.0 (10.8…13.3) 10.5 (8.9…12.1) 13.1 (12.0…14.3)

Engineering notes

x

  The flow switch QVE1902.0xx is not a safety component in terms of Directive

2006-42-EC.

x

  Operational safety of the supplied device is only guaranteed when used properly

(monitoring the flow of liquids). Under no circumstances may the indicated limit

values (see "Technical data") be exceeded.

x

  You must ensure that the materials used in the flow switch are sufficiently

chemically and mechanically durable against the medium to be monitored as

well as external influences.

x

  Comply with maximum contact load for the reed contact. The maximum contact

load indicated on the type label applies to Ohm loads only and may not be

exceeded under any circumstances.

High voltage or current spikes may occur when switching, in particular, inductive

or capacitive loads (e.g. relay coils, capacitors). Even a short overload may

destroy (fusing of contacts) or damage (reduced life cycle) reed contacts.

Use appropriate and tested safety measures.

x

  Select suitable measures to prevent the medium from freezing.

Do not operate, e.g. testing, the flow switch using pure water if operated in

ambient temperatures of <4°C. Residual water in the flow switch may result in

frost damage.

 Warning

Caution

Hindustan Hydraulics & Pneumatics,  Chennai - 01. 

Phone : 2534 3066, 2534 5625, 2534 5587
E-Mail : [email protected]

Contact person : V. Anandha krishnan - 98409 21885

Содержание QVE1902.010

Страница 1: ...act setting NO NC contact x Housing protection type IP 65 Protection class II x Maintenance free Use In HVAC plants to monitor the flow of liquid medium in hydraulic systems in particular refrigeration heat pump and heating plants e g for evaporators boilers heat exchangers etc Hindustan Hydraulics Pneumatics Chennai 01 Phone 2534 3066 2534 5625 2534 5587 E Mail hhp hindustanhydraulic in Contact p...

Страница 2: ...nder no circumstances may the indicated limit values see Technical data be exceeded x You must ensure that the materials used in the flow switch are sufficiently chemically and mechanically durable against the medium to be monitored as well as external influences x Comply with maximum contact load for the reed contact The maximum contact load indicated on the type label applies to Ohm loads only a...

Страница 3: ...ng that the arrow points parallel to the pipe axis and indicates the direction of flow x Install the section of piping for the flow switch the same as a valve in the existing piping Installation notes x Comply with all local regulations on electrical systems x Only qualified personnel may do the electrical installation x Always de energize the system before connecting the wires of the mains cable ...

Страница 4: ...int Adjust to the arrowhead means Switching point is at a lower flow rate Adjust to the arrow end Switching point is at a higher flow rate x Carefully retighten the locking screw x We recommend using thread locker to secure the locking screw on the switching unit after carrying out individual adjustments NO contact red arrow NC white arrow Operating notes x Please make sure that there are no exter...

Страница 5: ...ent Setting range Manual set at the factory to the middle of the setting range See Sizing on page 2 Protection class Housing II according to EN 60730 1 IP65 according to EN 60529 Storage transportation operation Temperature Humidity 0 70 C 95 r h Product standard EN 60204 1 Safety of machinery Electrical equipment of machines EU Conformity CE CM1T1596xx The product environmental declaration CE1E15...

Страница 6: ...15 46 0 105 5 239 QVE1902 025 DN 25 130 G1 15 55 5 115 5 315 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2017 Delivery and technical specifications subject to change Hindustan Hydraulics Pneumatics Chennai 01 Phone 2534 3066 2534 5...

Отзывы: