Web Server OZW672... V6.0
CE1C5712en
Building Technologies
Trend functions
2015-10-13
3. Select the query interval (1 s, 2 s, 5 s, 10 s, 15 s, 30 s, 1 m, 2 m, 5 m,
10 m, 15 m, 30 m, 1 h, 2 h, 3 h, 6 h, 12 h, 24 h).
4. Click to add a data point. The
Data point address
window is displayed
with available devices.
5. To record the outside temperature, data point "Outside temperature" under
"RVS43.143/109 > Info" is used in this example.
6. The Trend settings and the resulting maximum Trend length and bus load
are displayed in the "Edit" window.
Click to add up to a maximum of 100 data points.
To finish, confirm the settings with
OK
.