Document No. 129-402
Installation Instructions
June 6, 2018
Siemens Industry, Inc.
Page
3 of 5
Wiring Diagrams
NOTE:
All wiring must conform to NEC and local codes and regulations.
24 Vac/dc
Function
Color
Supply
Red
Neutral
Black
Ground
Green
120 Vac
Function
Color
Line
Black
Neutral
White
Ground
Green
230 Vac
CAUTION:
The actuator must be wired
with a 230 Vac line with
respect to neutral. The
ground lead must be
connected for proper
protection of the actuator.
Any other connection, such
as phase-to-phase, can
damage the actuator.
Function
Color
Line
Brown
Neutral Blue
Ground Green
Fixed Dual
End Switches
Switch
Wire
Color
Switch
Makes
Switch
Breaks
5°
Gray
< 5°
> 5°
85°
Yellow >
85°
< 85°
NOTE
:
Both sets of contacts are open when actuator
is between 5° and 85°.
CAUTION:
Mixed switch operation to the switching outputs
of both dual end switches (5° and 85°) is not
permitted.
Either AC line voltage from the same phase
must be applied to all four outputs of the fixed
dual end switches, or UL-Class 2 voltage must
be applied to all four outputs.