Document No. 129-402
Installation Instructions
June 6, 2018

Page

4 of 5

Siemens Industry, Inc.

Wiring, Continued

Electronic

Fusible Link

(EFL)

Figure 9.  GND EFL Models Come Pre-wired for Assembly.

NOTE:

The GND models pre-wired for assembly with the EFL (GNDxxx.1U/F) will only operate when an EFL,
(ASK79.xxx) is attached.

Maintenance

CAUTION:

The GND actuator does not require any periodic cycling to function properly as an integral part of an
active smoke control damper system.

The National Fire Alarm Code NFPA 72 states that all life

safety systems are to be functionally checked at least annually.

Check the smoke control

damper/actuator every time you functionally check your smoke detectors, emergency lights, and/or
power generators for operation.

Electronic Fusible Link (EFL)

Versions GNDxxx.1U/F contain wire with a Molex connector (See Figure 9) to accommodate an EFL.
EFLs are purchased separately. See Table 1.

Table 1. Electronic Fusible Link Product Numbers.

Part 

Number  Operation

ASK79.165

165°F (74°C)

ASK79.212

212°F (100°C)

ASK79.250

250°F (121°C)

ASK79.350

350°F (177°C)

Notice top position
of clip before
attempting to
couple with
sensor.

Molex connector

for use with

Siemens EFL.

Содержание OpenAir GND12x.1 Series

Страница 1: ...nic damper actuator Actuator is intended for control of approved fire and smoke leakage rated HVAC dampers Product Numbers GND12x 1x GND22x 1x GND32x 1x Warning Caution Notations WARNING Personal injury or loss of life may occur if you do not follow a procedure as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Required Tools 3 mm hex wren...

Страница 2: ...t through housing ear 2 Insert screw through eyelet and tighten using 1 4 inch 32 mm hex driver Figure 7 Tighten Conduit Screws No 2 Phillips Driver Manual Override For adjustment of the damper actuator when there is no power Figure 8 Manual Override CAUTION Apply 60 in lb to 90 in lb 7 Nm to10 Nm maximum torque to the shaft fixation set screws All four screws must be tightened CAUTION Always turn...

Страница 3: ... connected for proper protection of the actuator Any other connection such as phase to phase can damage the actuator Function Color Line Brown Neutral Blue Ground Green Fixed Dual End Switches Switch Wire Color Switch Makes Switch Breaks 5 Gray 5 5 85 Yellow 85 85 NOTE Both sets of contacts are open when actuator is between 5 and 85 CAUTION Mixed switch operation to the switching outputs of both d...

Страница 4: ...e Alarm Code NFPA 72 states that all life safety systems are to be functionally checked at least annually Check the smoke control damper actuator every time you functionally check your smoke detectors emergency lights and or power generators for operation Electronic Fusible Link EFL Versions GNDxxx 1U F contain wire with a Molex connector See Figure 9 to accommodate an EFL EFLs are purchased separ...

Страница 5: ...f their respective owners 2018 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt sbt siemens com Document No 129 402 Printed in the USA Page 5 of 5 Dimensions Figure 10 Dimensions of GND OpenAir...

Отзывы: