KNX Group Objects 

 

 

 

No.  Name in ETS 

Object 
function  

Flags 

Data point type KNX 

Range 

C  R  W  T  U  ID 

DPT_Name 

Format  Unit 

Fault information 

Transmit 

1  1 

1  0 

219.001 

_AlarmInfo 

6 Byte 

--- 

cf. Description below 

Fault state 

Transmit 

1  1 

1  0 

1.005 

_Alarm 

1 bit 

--- 

0 = No alarm 
1 = Alarm 

Fault transmission 

Receive 

1  0 

0  1 

1.003 

_Enable 

1 bit 

--- 

0 = Disable 
1 = Enable 

Setpoint 

Receive 

1  1 

0  1 

5.001 

_Scaling 

1 Byte 

0…100% 

Damper position 

Transmit

 

1  1 

1  0 

5.001 

_ Scaling 

1 Byte 

0...100% 

Overridden 

Transmit

 

1  1 

1  0 

1.002 

_Bool 

1 bit 

--- 

0 = False 
1 = True 

10 

Override position 1 

Receive

 

1  1 

0  1 

1.003 

_Enable 

1 bit 

--- 

0 = Disable 
1 = Enable 

11 

Override position 2 

Receive

 

1  1 

0  1 

1.003 

_Enable 

1 bit 

--- 

0 = Disable 
1 = Enable 

12 

Opening direction 

Read-only 

1  1 

0  0 

1.012 

_Invert 

1 bit 

--- 

0 = Not Inverted 
1 = Inverted 

Содержание OpenAir GDB111.1E/KN

Страница 1: ... OpenAir Communicative Damper Actuators KNX PL Link G B111 1E KN Damper actuators 5 10 Nm with KNX communication GDB111 1E KN with 5 Nm nominal torque GLB111 1E KN with 10 Nm nominal torque Operating voltage AC 24 V Supports KNX S Mode LTE Mode and PL Link s ...

Страница 2: ...ol www knx org ABT 4 0 2 Software Desigo Engineering Commissioning Tool A6V11159913 2 Release planned for April 2020 Product and software versions Product revision Series A Production period From 02 2020 Bus module FW version 4 25 ETS device profile v1d0 knxprod The ETS device profile can be downloaded at the following Internet address http siemens com hvac td Product documentation Title Topic Doc...

Страница 3: ... rotation bracket Mounting positions IP54 protection in following mounting positions Accessory mounting holes 2 Cf mounting instr M4634 2 Not to be used for fixation of the actuator use anti rotation bracket instead Maintenance The damper actuators are maintenance free Disconnect the electrical connections from the terminals if you want to work at the device Disposal The device is considered elect...

Страница 4: ...flashing a Factory reset in progress b When a connection test was triggered wait 4 Red steady a Device is in programming addressing mode b When a connection test was triggered Connection test failed 4 4 Function or part of the function available in PL Link operation only Addressing and bus test with push button The damper actuators can be set into addressing programming mode by push button Press p...

Страница 5: ...d no setpoint received within the defined time interval Backup position Actuator drives to defined position Keep last position Actuator keeps position without flow control Backup position Backup position 0 100 Position the damper drives to in case of communication interruption 50 Tab card advanced Hysteresis COV damper position 1 20 Threshold for the damper position COV below this value are not se...

Страница 6: ...arm 1 Alarm 3 Fault transmission Receive 1 0 1 0 1 1 003 _Enable 1 bit 0 Disable 1 Enable 4 Setpoint Receive 1 1 1 0 1 5 001 _Scaling 1 Byte 0 100 5 Damper position Transmit 1 1 0 1 0 5 001 _ Scaling 1 Byte 0 100 9 Overridden Transmit 1 1 0 1 0 1 002 _Bool 1 bit 0 False 1 True 10 Override position 1 Receive 1 1 1 0 1 1 003 _Enable 1 bit 0 Disable 1 Enable 11 Override position 2 Receive 1 1 1 0 1 1...

Страница 7: ...sensitivity 2 Fault state Indicates whether the actuator is in fault state If yes read out group object 1 3 Fault transmission Enabling disabling the fault transmission Fault transmission is disabled by default no faults are transmitted from the actuator over the KNX bus 4 Setpoint Setpoint 0 100 for volume flow or position depending on the operating mode 5 Damper position Relative damper position...

Страница 8: ...ion cables Cable length 0 9 m Power supply Number of cores and cross sectional area 2 x 0 75 mm2 Communication Number of cores and cross sectional area 2 x 0 75 mm2 Communication Communication protocol Connection type KNX TP galvanically isolated Bus load 5 mA Degree of protection Degree of protection Degree of protection acc to EN 60529 see mounting instruction IP54 Safety class Safety class acc ...

Страница 9: ...g Dimensions 71 x 137 x 61 mm Suitable drive shafts Round shaft with centering element 8 16 mm 8 10 mm Square shaft 6 12 8 mm Min drive shaft length 30 mm Max shaft hardness 300 HV 1 The documents can be downloaded from http siemens com bt download Diagrams Internal diagrams The damper actuator is supplied with two prewired cables Dp G CE CE 1 1 2 G0 2 3547G01 Tool Power supply and communication c...

Страница 10: ...heilerstrasse 1a 6300 Zug Switzerland Tel 41 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11753386_en _a Edition 2020 02 25 Dimensions Measurements in mm ...

Отзывы: