Commissioning and parameterization
The following parameters are checked or set during engineering and commissioning in the
ETS engineering tool.
Parameter
Range
Description
Factory settings
Tab card “standard”
Adaptive positioning On / Off
Adaption of actual (if mechanically limited)
opening range to position feedback 0...100%
Off = No adaption / On = Adaption active
Off
Backup timeout
0..60 min
0 min = disabled
Time interval to detect communication
interruption.
If disabled, the actuator drives to the last received
setpoint until a new valid setpoint is received.
30 min.
Backup mode
Backup position
Keep last position
Actuator behavior when the communication
timeout has been exceeded (no setpoint received
within the defined time interval).
▪
Backup position: Actuator drives to defined
position
▪
Keep last position: Actuator keeps position
without flow control
Backup position
Backup position
0…100%
Position the damper drives to in case of
communication interruption
50%
Tab card “advanced”
Hysteresis (COV)
damper position
1...20%
Threshold for the damper position. COV below
this value are not sent over the bus
1%
Min. repetition time
damper position
10...900 s
Minimum waiting time until a COV above the
hysteresis threshold is sent over the bus
10 s
Minimum damper
position
0...100%
Electronic lower position limit
0%
Maximum damper
position
0…100%
Electronic upper position limit
100%
Override position 1
0...100%
Damper position which can be triggered by the
corresponding group object (with override priority)
0%
Override position 2
0…100%
Damper position which can be triggered by the
corresponding group object (with override priority)
100%