4 / 10
Siemens
A6V11753386_en--_a
Smart Infrastructure
2020-02-25
HMI (Human-Machine Interface)
Push-button operation
Activity
Push-button operation
Confirmation
Enter / leave addressing mode
Press button <1 s
LED turns red or turns off
Reset to factory settings
Press button >20 s
LED flashes orange until device restarts
PL-Link connection test
4)
Press key >2 s and <20 s
LED flashes orange 1x
LED colors and patterns
Color
Pattern
Description
Off
---
Fault free operation or device not powered
Green
steady
Connection test successful
4)
Orange
flashing
a) Factory reset in progress
b) When a connection test was triggered: wait
4)
Red
steady
a) Device is in programming/addressing mode
b) When a connection test was triggered: Connection test failed
4)
4)
Function or part of the function available in PL-Link operation only
Addressing and bus test with push button
The damper actuators can be set into addressing/programming mode by push-button:
▪
Press push button (>0.1 s and <1 s)
▪
KNX bus wiring OK
→
LED turns red until addressing/programming is finished
▪
KNX bus wiring not OK
→
LED stays dark
Reset with push button
The damper actuators can be reset to the OEM default values by push-button:
▪
Press push button > 20s
▪
LED flashes orange
▪
Device restarts
All parameters are set to factory settings.