42
Min. val. inp 1 _ _ _ _ _mV
Max. val. inp 1 _ _ _ _ _mV
Min. val. mon 1 _ _ _ _ _ _ _
Max. val. mon 1 _ _ _ _ _ _
Enter the values for input 1
E.G.
Min. value inp. 1
Max. value inp. 1
Min. val. vis. 1
Max. val. vis. 1
In the example shown on the left a sen-
sor to measure the air speed has been
inserted.
A speed of 0 m/sec. is associated with
the value 0 mV.
A speed of 20 m/sec. is associated with
the value 10000 mV.
When the input is measured, the sensor
will supply a voltage of 5000 mV, at
which point the speed shown will be 10
m/sec.
Z2
5
GENERAL SETTINGS
Press
GENERAL SETTINGS
Over temp
_ _ _
Under t.
_ _ _
Max hum
_ _ _
Min hum
_ _ _
In order to set the alarm parameters,
please refer to paragraph 2.5 (HOW TO
SET THE SOFTWARE ALARMS).
These fields are present only in some
versions of the programme. They enable
relative humidity values (min. and max.)
to be set and they are lit by a warning
signal.
E.g.: this is useful when your specimens
must not remain at high and/or low
relative humidity.
Z1
Min. val. inp 2 _ _ _ _ _mV
Max. val. inp 2 _ _ _ _ _mV
Min. val. mon 2 _ _ _ _ _ _ _
Max. val. mon 2 _ _ _ _ _ _
Z3
Min. val. inp 3 _ _ _ _ _mV
Max. val. inp 3 _ _ _ _ _mV
Min. val. mon 3 _ _ _ _ _ _ _
Max. val. mon3 _ _ _ _ _ _
Z4
Min. val. inp4 _ _ _ _ _mV
Max. val. inp4 _ _ _ _ _mV
Min. val. mon4 _ _ _ _ _ _ _
Max. val. mon4 _ _ _ _ _ _
Z5
Min. val. inp5 _ _ _ _ _mV
Max. val. inp5 _ _ _ _ _mV
Min. val. mon5 _ _ _ _ _ _ _
Max. val. mon5 _ _ _ _ _ _
Z6
Min. val. inp6 _ _ _ _ _mV
Max. val. inp6 _ _ _ _ _mV
Min. val. mon6 _ _ _ _ _ _ _
Max. val. mon6 _ _ _ _ _ _
Z7
The following instructions refer to machines equipped with special connectors or analog IN/OUT sockets.
They may be controlled by devices such as PT100 probes or proportional signals.
K4
5.1
USER ANALOG INPUT CONFIGURATION (FROM 1 TO 6)