![Siemens OOH740-A9-Ex Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/siemens/ooh740-a9-ex/ooh740-a9-ex_technical-manual_383398055.webp)
Mounting/Installation
5
Connecting the detector base
55
Building Technologies
A6V10367521_h_en_--
Fire Safety
2015-02-02
The detector bases contain a spring clip. Permissible wire/strand cross-section
0.28...1.5 mm².
!
30°
1
3
4
5
6
7
2
Cable entry in detector base
1 The conductor loops must be placed
flat in the base bottom.
5 Contact for test tips
2 The conductor loops must not be
placed over this zone, as otherwise
the detector cannot be inserted
correctly.
6 Turn the screwdriver 90° in the
direction of the arrow to remove the
conductor or insert a strand.
3 Screwless connection terminals
7 Optimum insertion of the wire without
tool, at an angle of approx. 30°
4 Bare length 6.5...7.5 mm
5.10.1 Connection terminal DBZ1190-AB
Use the connection terminal DBZ11900-AB for multiple connections.
DBZ1190-AB
FDB2x1
FDB2x2
2
1
Installing connection terminals in the detector base
1 Connection terminals
2 Detector base