Mounting/Installation
Required space
46
Building Technologies
A6V10367521_h_en_--
Fire Safety
2015-02-02
5.1 Required space
l
Upon insertion of the detector, the detector base is stressed by compression,
tension and torsion. The fixing must thus be designed accordingly.
l
Detector bases must be placed flat on the ceiling.
l
Avoid mounting on steps, concrete ribs, etc.
l
Install the detector base directly on the recessed box, or together with a base
attachment, when the supply lead is surface-mounted and the cable diameter is
more than 6 mm.
l
There must be at least 50 cm of free space below and at least 2 cm to the
sides of the detector, so that the detector can be removed with the detector
exchanger.
l
Contorted detector bases complicate or even impede the insertion of the
detectors with the detector exchanger.
* = min. 2 cm
*
*
*
Minimum spacing when installing detector bases
WARNING
Using non-intrinsically safe devices in areas at risk of explosion
Risk of explosion
●
Do not use the detector exchanger and tester FDUD292 or the intelligent
detector tester FDUD293 in areas at risk of explosion.