Planning
4
Parameter sets for addressed operation
37
Building Technologies
A6V10367521_h_en_--
Fire Safety
2015-02-02
4.3.1.3 Specification
The following table shows the properties of the parameter sets for the point
detector in sensor mode 0:
No.
Name
Optical
Thermal
Typ. Response
time
from - typ. - to
Sensitivity,
open fire
Sensitivity,
smoldering fire
Static
activation
temperature
Differential activation
temperature
2
Differential
activation
possible from:
[s]
[%/m]
[%/m]
[°C]
∆
T [K]
[°C]
8
High Suppression
60 - 80 - 360
2.3
8
80
25
30
5
Suppression
90 -160 - 760
3.2
11.4
80
29
30
7
and
0
1
High Compensation
80
3.2
11.4
80
29
30
2
Robust
80
3.2
11.4
80
29
30
4
Balanced
40 - 64 - 300
2.3
8
80
25
30
6
Fast Response
20 - 30
1.6
5.6
80
22
3
9
High Sensitive Fast
20 - 30
0.8
2.8
60
16
3
14
Application-specific parameter sets
15
1
Default parameter set
2
Applicable with fast temperature increases >10 K/min.
All parameter sets except for 8, 14, and 15 comply with standards EN 54-7 and
CEA 4021.