7 Configuration
The following picture gives an overview about the configuration workflow.
There are basically three configuration steps:
1. Configure the fire detection with Sinteso Works
(or Cerberus-Engineering-Tool) and download the fire system.
Then, export the configuration in SiB-X format.
2. Configure the NK8237 in Composer and import the SiB-X file.
If requested, the Modbus mapping can be customized. Download the configura-
tion to the NK8237. Export the Modbus mapping table in CSV format.
3. The Modbus device needs to be configured by the integrator based on the
information provided in the Modbus mapping table (CSV export file).
The following chapters describe the configuration steps in detail.
7.1
Configuration checklist
Verify that you have satisfied the items needed in the first checklist before proceed-
ing to the configuration checklist that follows.
The following abbreviations are used the checklists:
DMS-CG
– DMS8000 Network, Fire & Intrusion Connectivity Guide (document
no. A6V10062425)
DMS-ICC
- Product-specific (e.g. MM8000) Installation, Configuration & Com-
missioning guide
Items needed for configuration
All FS20/FS720 Stations are equipped with the
a
FCA2013-A1 License key L2
(A5Q00018857) for enabling the BACnet protocol.
FS20/FS720 System commissioned. SiB-X export file available.
Danger Management software installed (at least Composer)
see
DMS-ICC
To set the IP address(es) on NK8237, NW8202 is required
p. 28
NK8237 unit(s) must be installed.
The network configuration must be defined, including all IP addresses, IP masks
and the default gateway.
If multiple routing is required, each route should be defined, including the destina-
tion IP address, mask, and gateway.
Engineering
tools
Automation level
Field level
BACnet/IP
Modbus Slave
BACnet client
BACnet server
Modbus Master
FC2020
GAP
Modbus RTU (RS-232)
ETH1
Ethernet
Modbus GW
Modbus device
Sinteso Works
Composer
SiB-X
CSV
3rd party configuration tool
Engineering data export
Configuration download
1
2
3