Siemens Industry, Inc.
87
6) Read voltages on the PDS receptacle inside the cabinet. If voltages are right, install
MJ- panel as below.
Installing the MJ- Control Panel
7) Remove the hinges from the Siemens MJ- control panel (left side) and install the
capture strip included in the retrofit kit. Install the retrofit hinges on the right side of
the MJ- panel.
8) Install the MJ- control panel to the GE cabinet using the pins removed from the hinges
in step 4 above.
9) Connect PDS plug on the MJ- to PDS receptacle in cabinet and tighten wing nuts.
GE Terminal #
MJ-
Notes
Description
NN31
U12
(switches gnd)
Neutral Pos. Switch
---
P2
---
NN23
C2
Load Current Pol.
NN26
E
Jumper to cabinet
gnd stud
Ground
NN10
E
Ground
NN24
E1
Load Current Non-
Polarity
NN9
U2
Jumper to NN20,
21, or 22)
Load Potential
NN27
J
(switches hot)
Raise Output
NN28
K
(switches hot)
Lower Output
NN30
U10
(switches gnd)
Operation Counter
NN29
U11
(switches hot)
Drag Hand Reset
NN20*
---
See steps 2 and 7
NN21*
---
See steps 2 and 7
NN22*
---
See steps 2 and 7
NN32
---
No connection