4 Setting Up the MJ-5 Control Panel
Siemens Industry, Inc.
34
Table 4.10
Communications Module Configuration Items
DATA ITEMS
DESCRIPTION
SELECTIONS
DatPortBaud
Local Data Port transmission rate
300, 1200, 2400, 4800,
9600
, or 19200
Data Parity
Local Data Port Parity Setting
EVEN
or NONE
DataPortAddr
Enables/Disables Addressing for Data Port
OFF
or ON
Reg ID
Regulator Identification Number (Note: This is NOT the address for
Data Port Communications)
NNNNN (Range
0-
32765)
Protocol
Communications Module Protocol
DNP3.0,
2200, 2200NPA, MJ3A A, MJ3A B1, MJ3A
B2, 2179, and Special
CommBaud
Communications Module transmission rate
300,1200,2400,4800,
9600
or 19,200
CommParity
Communications Module Protocol
NONE
, EVEN, ODD
CommAddr
Communications Module Address
NNNN (range:
0
-32765)
Resync Time
Communications Module resync time (in characters). Used for
Communications Module protocols 2200 and 2179 to determine
when one message ends and another message begins
NNN (range 0-250,
1
)
TxEnDelay
Communications Module Transmit Enable Delay (in milliseconds),
Specifies the amount of time between the RTS output being activated
and the start of transmit (output) data.
NNN (range
0
-250)
DnpDlConfirm
DNP Data Link Confirm
Y or
N
SW repeat
Enable Fiber loop
Y or
N
HostAddr
Host Address for Unsolicited Responses
NNN (range
0
-65535)
CMUnsolicited
Unsolicited Responses
Y or
N
AutoInhEnable
Auto Inhibit Enables (Y) Remote Raise/Lower. If disabled, (N)
activates automatic operation
Y or
N
DNP set
Select a predefined or custom DNP point set
DNPcfg.
2x3, 2x4, etc.
Deadband CL-1
Class 1--Used to set band without configuration tool
00.0
or NN.N
Deadband CL-2
Class 2---Used to set band without configuration tool
00.0
or NN.N
Deadband CL-3
Class 3---Used to set band without configuration tool
00.0
or NN.N
CommType
Describes the type of communication
Network,
Serial, Fiber-serial or RS-485
IP config
Enables/Disables IP Configuration Selection
Static
or DHCP
IP-192:168:001:200
Displays current IP address
192.168.1.200
or xxx.xxx.xxx.xxx
NM-
255:255:255:000
Displays current Network Mask
255.255.255.0
or
xxx.xxx.xxx.xxx
GW-
000:000:000:000
Displays current Gateway
192.168.1.1
or xxx.xxx.xxx.xxx
TCP port
DNP Communication Port Number
20,000
or NN,NNN (not advisable to change)
Note:
If both the Data Port and the Communications
Module are simultaneously set up for remote communications, then the Data Port restrictions
on the value of the “Comm Addr” data item must apply.