Appendix M
:
Retrofitting onto a CL-5 Cooper
Siemens Industry, Inc.
81
Mounting Instructions
According to the Cooper (McGraw-Edison) Voltage Regulator Instruction Manual (S225-10-10,
12/00), the control panel may be removed while the voltage regulator is energized
.
Removing the Cooper Control Panel
Follow the Cooper (McGraw-Edison) instruction manual for removing the control panel, which
should include, but is not limited to the following steps.
1) Make sure the Cooper control panel is not in the process of changing the tap
position.
2) Turn supervisory switch to
OFF
, turn Auto/Remote-Off-Manual switch to
OFF
,
wait 10 seconds.
3) Turn control panel power (Internal-Off-External Switch) to the
OFF
position.
4) Remove all fuses from the Cooper control panel.
5) Unscrew the thumbscrews holding the Cooper control panel in place, and swing
the control panel outward.
6) Close (push in) the current shorting knife-
blade switch “C” located at the back of
the control panel enclosure. This shorts out the secondary of the regulator CT.
Warning! Push the C shorting switch closed before attempting to remove the
fanning strip. Failure to do so will open the regulator CT circuit and may
produce a flashover in the control.
7) Open (pull out) the voltage knife-
blade switch “V1” (and “V6” if present). These
switches are located at the back of the control panel enclosure.
8) Loosen the screws on the interconnecting terminal block (located at bottom of
Cooper control enclosure).
9) Remove the fanning strip free from the terminal block.
10) Disconnect the front panel ground lead from the back of the Cooper control
enclosure.
11) Remove the Cooper control panel from the hinges and set the control panel
aside.
Installing the MJ- Control Panel
As a guide, follow the Siemens MJ- instruction manual.
1) Turn MJ- power switch to OFF and remove fuses before starting installation.
2) On MJ-, remove wiring from bottom terminal block to remove PDS plug and wires
from the control panel.
3) Install retrofit wiring as labeled to MJ- (table below) and tighten all screws,
including those not used. On the MJ- terminal block, terminal P2A-1 starts at the
left side of the bottom terminal block.