Appendix K
:
MJ-5 Operating Procedures
Siemens Industry, Inc.
76
K: MJ-5 Operating Procedures
Use the following instructions as a quick reference for
performing many of the standard MJ-5 operating
procedures.
View Instantaneous Load Voltage (Vld)
1.
Press Menu key twice
2.
Press Down Arrow once
3.
Read voltage (Vld) on display
View/Set Forward Voltage Level Value
1.
Press Voltage Level Fast-Path key
2.
Read Voltage Level on display
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
desired voltage on display - flashing digit will change
6.
Press Change/Save key again to save the new Voltage
Level
View/Set Bandwidth Value
1.
Press Bandwidth Fast-Path key
2.
Read Bandwidth on display
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
desired bandwidth on display - flashing digit will
change
6.
Press Change/Save key to save the new Bandwidth
setting
View/Set Time Delay Value
1.
Press Time Delay Fast-Path key
2.
Read FWD time delay on display. For REV time delay
press the Time Delay button again.
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
time delay on display - flashing digit will change
6.
Press Change/Save key to save the new time delay
value
View/Reset Max/Min Values
1.
View Meter value or tap position
2.
Press Max/Min key once
3.
Read maximum and minimum values on display
4.
To reset maximum and minimum values on display,
press Cancel Reset key once
View/Set Line Drop Compensation Values
1.
Press Resistance Fast-Path key
2.
Read resistive compensation voltage (R) on display
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
compensation voltage on display - flashing digit will
change
6.
Press Change/Save key to save the new resistive
compensation voltage value
7.
Press Resistive Fast-Path key again
8.
Read Reverse resistive compensation voltage (R) on
display
9.
Repeat steps 3 to 6 above to set the resistive
compensation voltage
10.
Press Reactance Fast-Path key
11.
Read the Forward reactive compensation voltage (X)
on display
12.
Repeat steps 3 to 6 above to set the Forward reactive
compensation voltage
13.
Press Reactance Fast-Path key again
14.
Read Reverse reactive compensation voltage (X) on
display
15.
Repeat steps 3 to 6 above to set the Reverse reactive
compensation voltage
View Operation Counter Values
1.
Press Operation Counter Select Fast-Path key (Op
Count)