Communications
11.6 Modems
BW500 and BW500/L
148
Operating Instructions, 12/2016, A5E33482052-AD
Master
Modem
●
auto answer off (dip switch?)
●
load factory default (dip switch?)
●
no flow control (dip switch?)
●
baud rate = 9600
●
10 data bits (probably the default)
Modbus RTU Software
●
baud rate = 9600
●
8 bit
●
no parity
●
1 stop bit
●
dial prefix: ATDT
●
Initialization command: ATE0Q0V1X05=0512=100
●
Reset command: ATZ
●
Hang-up command: ATHO
●
Command response delay: 5 seconds
●
Answer Delay: 30 seconds
●
Inter-character delay: 55 ms
Slave
Modem
●
auto answer on (dip switch?)
●
load factory default (dip switch?)
●
no flow control (dip switch?)
●
baud rate = 9600
●
10 data bits (probably the default)
Содержание Milltronics BW500
Страница 1: ...Operating Instructions Milltronics BW500 and BW500 L 12 2016 Edition Integrators ...
Страница 12: ...Table of contents BW500 and BW500 L 10 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 14: ...Safety Notes BW500 and BW500 L 12 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 16: ...The Manual BW500 and BW500 L 14 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 48: ......
Страница 68: ...Start Up 6 4 Load Cell Balancing BW500 and BW500 L 66 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 108: ...Operation 8 10 Totalization BW500 and BW500 L 106 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 153: ...Communications 11 7 Error Handling BW500 and BW500 L Operating Instructions 12 2016 A5E33482052 AD 151 ...
Страница 154: ......
Страница 198: ...Troubleshooting 13 2 Specifically BW500 and BW500 L 196 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 208: ...Appendix A 3 Technical support BW500 and BW500 L 206 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 218: ...Index BW500 and BW500 L 216 Operating Instructions 12 2016 A5E33482052 AD ...
Страница 219: ......