Troubleshooting
message
diagnosis
action
E1 (program)
security code required
enter access code into P000
E2 (run)
totalizer resolution too low increase value (P631 - P639)
E3 (run)
zero out of range
consider an initial zero P377,
refer to
Recalibration/Initial
Zero
on page 33
E4 (run)
span out of range
consider an initial span P388,
refer to
Recalibration/Initial
Span
on
page 36
E5 (run)
parameter not entered
check parameters P005 - P017
for entry
E6 (run)
zero calibration required
do a zero calibration
E7 (run)
span calibration required
do a span calibration
E8 (program)
parameter value error
check that value is valid
E9(run)
auto zero out of range
auto zero has accumulated
deviation beyond 2% from last
operator initial zero. If error is
not caused by material on belt,
then do an operator initiated
zero.
E10 (run)
rate or span out of range
loading on belt is 300% of rated
load or greater. Investigate and
if no mechanical cause, check
to see if re-rating the design
rate is required.
E11 (run)
speed greater than twice the
design speed
check design belt speed
against actual belt speed,
check speed constant, per-
form speed constant adjust
(P018) if necessary
E12 (factoring)
span out of range
test load is either too low or
beyond 100% of design load
(P952). Replace test weight
with a heavier or lighter weight
and try factoring again.