INTRODUCTION

The Model MDACT from Siemens Industry, Inc. is a
multipoint serial dialer for use in MXL and FireFinder-
XLS systems where point identification of alarm,
supervisory, status or trouble indication is required at
central stations.

The MDACT has the following features:

Multiple Data Protocols: Contact ID and SIA

100 Event History Buffer

Dual Phone Line Interface

Option Bus Interface for Built-in Programming
using DCT-P LCD Remote Keypad

LEDs for Heartbeat, System Trouble and Phone
Line Trouble (one per line)

Real Time Clock

NOTE: The NIM-2D Upgrade Kit, P/N 500-649576,

must be used.

The MDACT is compatible with the following:

• MMB ROM version 10.14 and higher

• SMB ROM version 6.14 and higher

• CSG-M version 11.05 and higher

• PMI version 4.0 and higher

• Zeus version 4.0 and higher

Installation Instructions

Model MDACT

MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator

P/N 315-099351-6

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

For MXL programming, refer to MXL Operation,
Installation, and Maintenance Manual, P/N 315-
092036, MXL-IQ Operation, Installation, and Mainte-
nance Manual, P/N 315-093624, CSG-M Manual,
P/N 315-090381, and CSG-M Version 11.05 Up-
date, P/N 315-099402, as applicable.

For FireFinder-XLS programming, refer to the
FireFinder-XLS Installation, Operation and Mainte-
nance Manual, P/N 315-033744, and the Zeus
Quick Start Manual, P/N 315-033875.

OPERATION

The MDACT delays the AC Fail trouble signal in
accordance with NFPA and UL requirements. Refer
to the MDACT Programming Manual, P/N 315-
099378 for further information.

INSTALLATION

Remove all system power before installation,
first battery and then AC. (
To power up, connect
the AC first, then the battery.)

The MDACT installs into the MXL optional MOM-4/-2
card cage where it occupies one half width slot. The

CABLE P/N 555-190967

TO MMB-2/-3, SMB-2/-3 OR PSR-1

TO MMB-2/-3, SMB-2/-3, PSR-1
24V

OR PSC-12

DO NOT USE

P7

P10

P5

P8

TB6

TB7

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1

1

1

1

1

1

P3

TB3

MDACT

TB4

INSTALLED IN MXL PANEL

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

P4

DO NOT USE

TB1

P1

TB2

P2

MDACT

MOM-4

NOTE:

MDACT can only be installed
in MOM-4/-2 slots P2 or P4.

Figure 1

MDACT Installation In MXL Panel

Содержание MDACT

Страница 1: ... programming refer to MXL Operation Installation and Maintenance Manual P N 315 092036 MXL IQ Operation Installation and Mainte nance Manual P N 315 093624 CSG M Manual P N 315 090381 and CSG M Version 11 05 Up date P N 315 099402 as applicable For FireFinder XLS programming refer to the FireFinder XLS Installation Operation and Mainte nance Manual P N 315 033744 and the Zeus Quick Start Manual P ...

Страница 2: ...N position P7 P10 P5 P8 TB6 TB7 1 1 1 1 1 1 MDACT TB4 INSTALLED IN FIREFINDER XLS PANEL 1 2 3 4 5 6 7 8 9 10 11 12 13 1415 16 1 2 3 4 5 6 7 8 9 10 11 12 13 1415 16 P4 TB2 P2 XMI DO NOT USE WITH FIREFINDER XLS SEE XMI INSTALLATION INSTRUCTIONS P N 315 034870 MOM 2 FOR FIREFINDER XLS ONLY MODEL MOM 2 IS AVAILABLE REQUIRES MOUNTING PLATE MOM2 XMP TO 24V PSC 12 DO NOT USE WITH FIREFINDER XLS SEE XMI I...

Страница 3: ...o the CSG M or Zeus configuration printout for the address of the module See Table 1 for MXL MNET and XLS HNET settings 2 Switch SW3 is factory set All switches must remain in the ON position 3 Set jumper plugs on JP4 to the M position 4 Set jumper plugs on P6 to the positions shown in Figure 3 Telephone Connectons Telephone Cord Installation Connect the primary phone line to the MDACT modu lar ja...

Страница 4: ...T meets the requirements of UL 1950 1 2 3 6 7 8 R1 T1 4 5 R T RJ31X Module Full Modular Phone Jack To Dialer Connecting the Keypad to the MDACT NOTE The DCT P LCD Remote Keypad is used strictly for programming and debugging purposes only A DCT P LCD Remote Keypad can be used to operate the MDACT Communicator Plug the molex connector from the DCT P onto the connector pins on the MDACT board as show...

Страница 5: ...MDACT Fire Communicator Available Reporting Formats Contact ID CID Is the preferred reporting format It provides a four digit account code followed by a three digit event code a two digit group number and a three digit contact number all of which are used to provide specific point identification SIA Security Industry Association SIA Digital Communication Standard The DACT provides level 1 compatib...

Страница 6: ...vailable Report Format Radionics D6500 Radionics D6600 Sur gard SG SLR Osborne Hoffman Quick Alert Model II Ademco 685 Silent Knight SK9000 Contact ID q q q q q SIA 300 q q q SIA 110 q q q Figure 7 MDACT UL Listed Compatibility ...

Страница 7: ...XOX OXXXOXXO OXXXOXXX 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOX...

Страница 8: ...P N 315 099351 6 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: