SYS TROUBLE

HEARTBEAT

Phone Line 1 LED

Phone Line 2 LED

System Trouble LED

Heartbeat LED

KEYPAD

No Connection

MDACT can be installed in either slot P2 or slot P4 of
the MOM-4/-2. (See Figure 1.) For FireFinder-XLS,
only the MOM-2 can be used. (See Figure 2.)

Setting the Switches

Set all switches, configuration jumpers, and connec-
tion cables before installing them into the MOM-4/-2.
See Figure 3 for switch locations.

1.

Use switch SW1 to set the MXL MNET or
FireFinder-XLS HNET network address. Set this
switch according to the address where the MDACT
is installed in the MXL or FireFinder-XLS network
map. Refer to the CSG-M or Zeus configuration
printout for the address of the module. See Table 1
for MXL (MNET) and XLS (HNET) settings.

2.

Switch SW3 is factory set. All switches must
remain in the ON position.

3.

Set jumper plugs on JP4 to the "M" position.

4.

Set jumper plugs on P6 to the positions shown in
Figure 3.

Telephone Connectons

Telephone Cord Installation

Connect the primary phone line to the MDACT modu-
lar jack "Line1" using a phone cord. Connect the
secondary phone line to the MDACT jack "LINE2"
using another phone cord. See Figure 4 for phone line
connection.

NOTE: You must connect separate primary and

secondary phone lines to the MDACT for all
applications.

Location

To prevent jamming of alarm and other reports, wire
and locate the RJ31X or RJ38X jack so that normal
phone use is temporarily interrupted while the MDACT
transmits data (See Figure 5). After installation,
confirm that the MDACT seizes the line, acquires dial
tone and reports correctly to the receiver.

Содержание MDACT

Страница 1: ... programming refer to MXL Operation Installation and Maintenance Manual P N 315 092036 MXL IQ Operation Installation and Mainte nance Manual P N 315 093624 CSG M Manual P N 315 090381 and CSG M Version 11 05 Up date P N 315 099402 as applicable For FireFinder XLS programming refer to the FireFinder XLS Installation Operation and Mainte nance Manual P N 315 033744 and the Zeus Quick Start Manual P ...

Страница 2: ...N position P7 P10 P5 P8 TB6 TB7 1 1 1 1 1 1 MDACT TB4 INSTALLED IN FIREFINDER XLS PANEL 1 2 3 4 5 6 7 8 9 10 11 12 13 1415 16 1 2 3 4 5 6 7 8 9 10 11 12 13 1415 16 P4 TB2 P2 XMI DO NOT USE WITH FIREFINDER XLS SEE XMI INSTALLATION INSTRUCTIONS P N 315 034870 MOM 2 FOR FIREFINDER XLS ONLY MODEL MOM 2 IS AVAILABLE REQUIRES MOUNTING PLATE MOM2 XMP TO 24V PSC 12 DO NOT USE WITH FIREFINDER XLS SEE XMI I...

Страница 3: ...o the CSG M or Zeus configuration printout for the address of the module See Table 1 for MXL MNET and XLS HNET settings 2 Switch SW3 is factory set All switches must remain in the ON position 3 Set jumper plugs on JP4 to the M position 4 Set jumper plugs on P6 to the positions shown in Figure 3 Telephone Connectons Telephone Cord Installation Connect the primary phone line to the MDACT modu lar ja...

Страница 4: ...T meets the requirements of UL 1950 1 2 3 6 7 8 R1 T1 4 5 R T RJ31X Module Full Modular Phone Jack To Dialer Connecting the Keypad to the MDACT NOTE The DCT P LCD Remote Keypad is used strictly for programming and debugging purposes only A DCT P LCD Remote Keypad can be used to operate the MDACT Communicator Plug the molex connector from the DCT P onto the connector pins on the MDACT board as show...

Страница 5: ...MDACT Fire Communicator Available Reporting Formats Contact ID CID Is the preferred reporting format It provides a four digit account code followed by a three digit event code a two digit group number and a three digit contact number all of which are used to provide specific point identification SIA Security Industry Association SIA Digital Communication Standard The DACT provides level 1 compatib...

Страница 6: ...vailable Report Format Radionics D6500 Radionics D6600 Sur gard SG SLR Osborne Hoffman Quick Alert Model II Ademco 685 Silent Knight SK9000 Contact ID q q q q q SIA 300 q q q SIA 110 q q q Figure 7 MDACT UL Listed Compatibility ...

Страница 7: ...XOX OXXXOXXO OXXXOXXX 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOX...

Страница 8: ...P N 315 099351 6 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: