MDACT can be installed in either slot P2 or slot P4 of
the MOM-4/-2. (See Figure 1.) For FireFinder-XLS,
only the MOM-2 can be used. (See Figure 2.)
Setting the Switches
Set all switches, configuration jumpers, and connec-
tion cables before installing them into the MOM-4/-2.
See Figure 3 for switch locations.
1.
Use switch SW1 to set the MXL MNET or
FireFinder-XLS HNET network address. Set this
switch according to the address where the MDACT
is installed in the MXL or FireFinder-XLS network
map. Refer to the CSG-M or Zeus configuration
printout for the address of the module. See Table 1
for MXL (MNET) and XLS (HNET) settings.
2.
Switch SW3 is factory set. All switches must
remain in the ON position.
3.
Set jumper plugs on JP4 to the "M" position.
4.
Set jumper plugs on P6 to the positions shown in
Figure 3.
Telephone Connectons
Telephone Cord Installation
Connect the primary phone line to the MDACT modu-
lar jack "Line1" using a phone cord. Connect the
secondary phone line to the MDACT jack "LINE2"
using another phone cord. See Figure 4 for phone line
connection.
NOTE: You must connect separate primary and
secondary phone lines to the MDACT for all
applications.
Location
To prevent jamming of alarm and other reports, wire
and locate the RJ31X or RJ38X jack so that normal
phone use is temporarily interrupted while the MDACT
transmits data (See Figure 5). After installation,
confirm that the MDACT seizes the line, acquires dial
tone and reports correctly to the receiver.