Technical specifications
7.2 Certificates and approvals
LOGO! CIM
Operating Manual, 10/2021, A5E51250518-AA
83
cULus Hazardous (Classified) Locations
Underwriters Laboratories, Inc.: CULUS Listed E472610 IND. CONT. EQ. FOR HAZ. LOC.
Applied standards:
•
UL 121201
•
CSA C22.2 No. 213-17
APPROVED for Use in:
•
Cl. 1, Div. 2, GP. A, B, C, D T4
•
Cl. 1, Zone 2, GP. IIC T4
Report / UL file: E472610
Installation Instructions for cULus haz.loc.
•
WARNING – Explosion Hazard – Do not disconnect while circuit is live unless area is known
to be non-hazardous.
•
WARNING - Explosion Hazard - Substitution of components may impair suitability for Class
I, Division 2 or Zone 2.
•
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class I, Zone 2,
Group IIC; or non-hazardous locations.
•
Antenna must be installed within the end use enclosure. Routing and remote installation
(not evaluated as part of this certification) of the antenna shall be in accordance with the
appropriate location regulations when installed in unclassified and/or Class I, Division 2
Hazardous Locations.
WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF
MATERIALS USED IN THE RELAYS.
FM
Factory Mutual Research (FM) in accordance with
Approval Standard Class Number 3611, 3600, 3810
ANSI/UL61010-1, ANSI/UL 121201
CAN/CSA-C22.2 No. 0-10
CSA C22.2 No. 213
CAN/CSA-C22.2 No. 61010-1
APPROVED for use in Class I, Division 2, Group A, B, C, D T4;
Class I, Zone 2, Group IIC Tx
Installation Instructions for FM
•
WARNING – Explosion Hazard – Do not disconnect while circuit is live unless area is
known to be non-hazardous.
•
WARNING - Explosion Hazard - Substitution of components may impair suitability for Class
I, Division 2 or Zone 2.