Web-based configuration
5.4 Web pages
LOGO! CIM
Operating Manual, 10/2021, A5E51250518-AA
57
⑥
Here you configure the properties of the connections that CIM work as S7 server.
•
Remote IP: the IP of the client that you want to connect
•
Local TSAP: the TASP in LOGO! CIM is 00.01 to FF.FF
•
Remote TSAP: the TSAP of the client that you want to connect
⑦
Here you configure the properties of the connections that CIM work as a S7 client
•
Remote IP: the IP of the server that you want to connect
•
Remote TSAP: the TSAP of the server that you want to connect
•
Local TSAP: the TASP in LOGO! CIM is 00.01 to FF.FF
⑧
Click to open the "Data transfer table" of the corresponding connection that CIM work as a S7 client.
Data transfer table configuration
For the connections that CIM works as S7 client, you need to configure the data transfer
table:
1.
Click "Add Row".
2.
Click
②
to choose the UDM address type of CIM.
3.
Input one address in the address field of CIM
③
.
4.
Click the
④
to choose data transfer directions.
5.
Click
⑤
to choose S7 address type of the remote S7 server.
6.
Input the S7 Start address of the remote S7 server
⑥
.
7.
Input the length of the Data
⑦
need to be transferred.
8.
To set the time interval that CIM synchronizes the data with the server, enable "Customized
Interval" and input the specified time interval
⑧
.
The default minimum transmit interval is 80 milli-second.