Installation notes
∂ Always run the high-voltage ignition cables separately from the unit and
other cables while observing the greatest possible distances
∂ When wiring, ensure that there is enough free space for the BCI connection jack
∂ Do not mix up phase and neutral conductors
Note!
For use in power supply systems with non-grounded neutral conductors!
Power supply systems with earthed neutral conductors form the basis of the
Β
systems with non-earthed neutral conductors, terminal 2 of the LFS1 must be connected to the
earth conductor via the RC unit ARC 4 668 9066 0 for ionization current supervision. It must be
made certain that local regulations are complied with (e.g., protection against electric shock) since
120 V AC (50 / 60 Hz) or 230 V AC (50
/ 60 Hz) mains voltage produces peak leakage
currents of 2.7 mA.
diagramsandcircuitdiagramsoftheLFS1inthisDataSheet.Inpower supply
Note!
Double insulation.
The flame safeguards LFS1 and the terminal bases AGK11.7 including separating plate
element are double-insulated between the terminal areas 1...7 and 9...12. This means
that they feature strengthened insulation; refer also to the
Technical data
Β
If the double insulation needs to be present up to the connected components, the
separating plate element included in the scope of delivery of the AGK11.7 must be
installed in all cases (marked with an arrow in the figure below). As an alternative,
other suitable measures can also be put in place. Safe separation can only be
ensured if all connected components are fitted with a safe separation facility and the
components have been wired as specified. In particular, compliance with the
relevant warning notes must be ensured.
chapter.
Separating plate element
7782z04en/1215
Note!
When using QRA2M and QRA10M!
Connect additional module AGK30 in accordance with connection diagram 7782a14.
Β
The ground terminal of plug-in base AGK11.7 (symbol
) must be
permanently connected to the burner ground. Additional module AGK30 must
always be connected within plug-
in base AGK11.7 in terminal areas 1…7.
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
7/40
Building Technologies CC1N7782en 18.04.2018