Technical data
(continued)
Range adjustment for flame sensitivity using
Switching threshold for switching on flame ON signal /
parameter 182:
Test level switching threshold for flame detector
ION
QRA2 / QRA2M /
RAR9
QRA4 / QRA4M /
QRA10 / QRA10M
Parameter 182 = 0
1µA/1µA¹)
12µA/12µA¹)
5µA/5µA¹)
Parameter 182 = 1
2µA/2µA
12µA/12µA
10µA/8µA
Parameter 182 = 2
4µA/4µA
12µA/12µA
20µA/18µA
12µA/12µA
Parameter 182 = 3
8µA/8µA
30µA/28µA
¹) Values printed in bold are the same as the factory settings