Communication, BCI interface
BCI interface
The BCI interface connection jacks are located on the underside in the LFS1 base
area; refer to the figure. Parameters can be set in accordance with the parameter
list below using the display and operating unit AZL2 and signal cable AGV50.
The signal cable AGV50 is preassembled and fitted with a RJ11 connector. When
connecting, ensure that the orientation is correct
– the clip on the RJ11 connector
must inserted into the notch on the connection jack. A click sound indicates that the
clip has locked into place. To disconnect the connection, open the clip by gently
tilting it towards the cable using your finger before pulling out the RJ11 connector.
BCI interface
connection jack
7
7
8
2
z
0
5
e
n
/1
2
1
5
The display and operating unit AZL2 with LCD display enables simple operation,
parameterization, and targeted diagnostics via menu-driven operation. When performing
diagnostics, the display shows the operating statuses, the type of error, and the startup
counter (IBZ). Passwords protect the different parameter levels for OEM (burner / boiler
manufacturer) and heating engineers (HF) against unauthorized access. Simple settings
that the plant operator can make on site do not require a password.
For detailed information on parameterization; refer to User Documentation
A7782,
Operation via AZL2
chapter.
For the parameters, their default settings, and their range adjustments at the
different access levels, refer to the following parameter list.