Diagnostics and maintenance
5.6 SNMP
IE/PB LINK PN IO
Operating Instructions, 11/2017, C79000-G8976-C393-02
75
5.6
SNMP
SNMP (Simple Network Management Protocol)
SNMP is a protocol for diagnostics and managing networks and nodes in the network. To
transmit data, SNMP uses the connectionless UDP protocol.
The information on the properties of SNMP-compliant devices is entered in MIB files (MIB =
Management Information Base).
You will find detailed information on SNMP and the Siemens Automation MIB in the manual
/5/ (Page 90).
For more detailed information on using MIB files, refer to the documentation of the SNMP
client you are using (example of an SNMP client: SNMP OPC server from SIMATIC NET).
Range of performance of the LINK
The LINK supports data queries using SNMP in version V1 (standard). The LINK returns the
content of certain MIB objects according to the MIB II standard and the part of the Siemens
Automation MIB relevant for the LINK.
Traps are not supported.
Supported MIBs in SNMPv1
The LINK supports the following MIBs and groups of MIB objects:
●
MIB II (acc. to RFC1213)
–
System
–
Interfaces
–
IP
–
ICMP
–
TCP
–
UDP
–
SNMP
The following groups of the standard MIB II are not supported:
–
AT
–
EGP
–
Transmission
●
LLDP MIB
Содержание IE/PB LINK PN IO
Страница 10: ...Table of contents IE PB LINK PN IO 10 Operating Instructions 11 2017 C79000 G8976 C393 02 ...
Страница 84: ...Approvals IE PB LINK PN IO 84 Operating Instructions 11 2017 C79000 G8976 C393 02 ...
Страница 88: ...Accessories A 2 C PLUGs IE PB LINK PN IO 88 Operating Instructions 11 2017 C79000 G8976 C393 02 ...
Страница 92: ...Index IE PB LINK PN IO 92 Operating Instructions 11 2017 C79000 G8976 C393 02 ...