5 / 14
A6V10881143_en--_c
Siemens
2019-04-25
Smart Infrastructure
HMI (Human-Machine Interface)
For more detailed explanations on device states, functions and error display, cf. product
documentation CE1Z4634
1)
.
Push-button operation
Activity
Push-button operation
Confirmation
Display current address
(in reverse order)
Press button < 1s
Current address is displayed
Enter Modbus address with push-button Press button > 1s and < 5s
See description next page
Enter push-button addressing mode
(for use with Climatix
TM
controllers)
Press button > 5s and < 10s
LED shines orange (release
button when red LED gets
dark). Timeout after 1 min.
Reset to factory settings
Press button > 10s
LED flashes orange
LED colors and patterns
Color
Pattern
Description
Green
steady
Start-up
1s on / 5s off
Fault free operation (“life pulse”)
flashing
Bus traffic
Orange / green
1s orange / 1s green Device is in override control
Orange
1s on / 1 off
Bus parameters not yet configured
Orange
1s on / 5s off
Backup mode entered
Red
Steady
Mechanical fault / device jammed
1s on / 5s off
Internal error
0.1s on / 1s off
Invalid configuration, e.g. Min = Max
Resetting the device by push button
The rotary actuators can be reset by push-button:
1. Press button for >10s
à
LED starts flashing
orange
2. Release button while LED still flashes
à
LED keeps flashing for 3s
3. If the button is pressed within these 3s, the reset is cancelled.
4. After those 3s
à
LED shines
red
(reset), then
green
(start-up).