Register 769 “Status”
Status
Bit 00
1 = Local override
Bit 06
1 = Adaption done
Bit 01
1 = Backup mode active
Bit 07
1 = Adaption in progress
Bit 02
1 = reserved
Bit 08
1 = Adaption error
Bit 03
1 = reserved
Bit 09
1 = Selftest failed
Bit 04
1 = Device jammed
Bit 10
1 = Selftest passed
Bit 05
1 = Nom. lifetime exceeded
Bit 11
1 = Invalid configuration
Supported function codes
Function codes
03 (0x03)
Read Holding Registers
04 (0x04)
Read Input Registers
06 (0x06)
Write Single Register
16 (0x10)
Write Multiple registers (Limitation: Max. 120 registers within one message)
Notes
Safety
Caution
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
●
Observe national provisions and comply with the appropriate safety regulations.
Mounting
●
Do not open the rotary actuators
Mounting positions, cf. mounting instr. A6V10920701