27/44
Siemens
Technische Grundlagen: Drehantriebe GEB...1
CM2Z4621en
Building Technologies
2017-05-26
0
∂
Alternative switch-on/switch-off of self-adaptation.
: ON
0: OFF
∂
Factory setting: 0.
2...
0...
∂
Alternate
setting:
2..: DC 2...10 V
0..: DC 0...10 V
∂
Factory setting: 0…
C
0
∂
Alternate
setting:
C: DC 0...35 V (Comfort, with characteristic function)
0: DC 0...10 V (without characteristic function)
∂
Factory setting: 0.
Self-adaptation
Positioning signal without
characteristic function:
(GEB161.1, GEB166.1)
Positioning signal
with/without characteristic
function:
(GEB163.1, GEB164.1)