8
Specifications
Technical data
38
Building Technologies
010095_j_en_--
Fire Safety
2013-02-22
External alarm indicators
Number of external alarm indicators that
can be connected
2
Voltage
DC 10…17 V
Current
9…15 mA
Length of line
Max. 30 m with unshielded cables
(recommended), or when the shielding is
connected to the positive pole of the AI on
the detector base
Max. 5 m, if the shielding is connected to
earth
Function
Number of sounds
11
Number of optical indicator patterns
1
Activation levels
2
Sound intensity
Depending on the set tone; see chapter
'Configuration' for details
Light intensity at 32 VDC
(depending on viewing angle
-30° … +30°):
FDS229-R: Red hood
FDS229-A: Orange hood
1.0 … 2.1 cd
Depending on the viewing angle, see 'Technical
data annex', sub-chapter 'FDS229-R, red'
0.9 … 1.8 cd
Depending on the viewing angle, see 'Technical
data annex', sub-chapter 'FDS229-A, orange'
Connections
Detector line:
Design
Plug-type connection
External alarm indicators:
Design
Plug-type connection
MC link:
Design
Proximity interface