Structure and function
3
Function
17
Building Technologies
010095_j_en_--
Fire Safety
2013-02-22
3.2.5
Diagnosis levels
The device largely monitors its function by itself. The following diagnosis levels are
taken from the different control measuring processes:
Normal
Fault
For details, see table below.
When a fatal error occurs, which impairs the proper function of the alarm sounder,
a fault message is signaled.
To correct the cause of the fault, additional information is available in the device.
The additional information can be displayed using e.g. the detector exchanger and
tester FDUD292 or the intelligent detector tester FDUD293.
You will find more information in documents 007227 and 009718.
Display
Meaning
Measures
'no deviation'
Normal, no fault is present
The alarm sounder is fully functional
None
Any fault message
Fault present
Invalid parameter settings
Alarm function no longer ensured
(Piezo element defective)
Set valid parameters
Replace alarm sounder
Supply error
Check detector line voltage
Exchange device
Software error (Watchdog error)
Exchange device
Memory error
Exchange device
Communication error involving device and
control panel
Remedy cause
The status 'Any fault message' can be displayed together with another status, e.g.
'needed excha.' (replacement necessary).