4
Undertaking modernization
Step 1: Detector modernization
22
Building Technologies
A6V10323158_d_en_--
Fire Safety
2015-04-09
4.1.3 Parameterization of detection characteristics
4.1.3.1 Collective detector lines and 'MS8/PMT' detector family
The sensor mode (0, 1, or 2) and/or detector type (optical, thermal, combined), and
the corresponding parameter set are selected using detector exchanger and
tester FDUD292.
You will find more information in document 007227.
You will find detailed information about the detector modes and parameter sets in
document 007004. See the chapter 'Applicable documents [
4.1.3.2 'AnalogPLUS' detector family
The multiple protocol detectors can be operated under AnalogPLUS with the
following parameter sets:
Operation as detector of type
Parameter set
default
Selection with
FDUD292
DO1131A
'Sensitive'
'Universal Fast'
DOT1131A
'Fast Response'
'Universal Fast'
DT1131A
'A1R'
- - -
DT1132A
'BS'
- - -
With detector exchanger and tester FDUD292, the 'Universal Fast' parameter set
can also be selected when replacing the DO1131A and DOT1131A detectors. This
parameter set is only available with the FDOOT241-A3 in AnalogPLUS mode.
The sensitivity of the 'Universal Fast' parameter set is comparable with the
sensitivity of the 'Balanced' parameter set. The response time of the 'Universal
Fast' parameter set is in the range <10 s in AnalogPLUS mode and is comparable
with the response time of the replaced AnalogPLUS detector. The quick response
increases sensitivity towards deceptive phenomena.
You will find detailed information about the detector modes and parameter sets in
document 007004. See the chapter 'Applicable documents [